Operating Instructions BA_045_2019-08_10.00  Changing module in PASCAL CV pressure transmitter

Page 3/7

BTA-No. 045  page 3

Placing the basic module in service after assembly 

-   After the installation work is completed, switch on the supply voltage.

-   The 2 device LEDs will flash alternately. This shows that the data in the basic module and the sensor do not match.

-   To adjust the data, press the right-hand button (SPAN).

-   The LEDs will stop flashing.

-   The pressure transmitter will be ready for operation after approximately 20 seconds.
If the device was being operated within a special measuring range, replacing the module will have caused these settings to be lost. 

This means that the device is now operating within the nominal range of the module and can be programmed for special measuring 

ranges (see BTA-028 operating instructions, page 5).
After a basic module has been replaced, the settings and programming for all modules are lost.

Example:

The nominal measuring range of the module is 0 to 4.0 bar, but the special range should be 1.0 to 2.5 bar.

 

To program the lower range value, proceed as follows:

 

In this example, the output current should be 4.0 mA at a pressure of 1.0 bar.

 

To set the device pressure to 1.0 bar, press and hold the ZERO button for approximately 4 seconds.

 

The ZERO LED will flash once to confirm the transfer of the new zero point.

 

To program the upper range value, proceed as follows:

 

In this example, the output current should be 20.0 mA at a pressure of 2.5 bar.

 

To set the device pressure to 2.5 bar, press and hold the SPAN button for approximately 4 seconds.

 

The SPAN LED will flash once to confirm the transfer of the new upper range value.

 

1.0 bar  

=  

0%  

=  

4.0 mA  

=  

lower range value

 

2.5 bar 

=  

100% 

=  

20.0 mA   =  

upper range value

Assembling the basic module 4 to 20 mA

Step 1

Place the sealing washer in position (Fig. 1).

Step 2

Hold the basic module at the side of the case housing and plug in the sensor con

-

nector. (Fig. 2).

Caution:

Avoid touching the plug connector at the bottom of the basic module with your 

fingers since dirt (grease, moisture) and electrostatic discharge could damage the 

device.

Step 3

Slip the basic module sideways over the rim and into the housing of the sensor 

module. (Fig. 3).

Step 4

Using a suitable screwdriver (with as wide a blade as possible), install the screws 

(3x19.5mm) at left and right of the basic module and tighten them down (Fig. 4). 

Connect the device lead. Then screw the device cap back on.

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Summary of Contents for PASCAL CV

Page 1: ...eps governing their installation and removal In addition to these operating instructions other information such as statutory requirements applicable standards supplemental technical speci cations in d...

Page 2: ...ly lift the basic module up and out of the housing Be sure that at the lower section of the module the ribbon cable for connecting the sensor to a plug connector remains attached Turn the basic module...

Page 3: ...t current should be 4 0 mA at a pressure of 1 0 bar To set the device pressure to 1 0 bar press and hold the ZERO button for approximately 4 seconds The ZERO LED will ash once to con rm the transfer o...

Page 4: ...AL CV follow Step 1 above and Steps 3 and 4 below Step 3 Position a new switching module on the basic module Insert the switching module into the basic module Be sure to press evenly and carefully Usi...

Page 5: ...CV with a new display module follow Step 1 above and Step 4 below Step 4 Position a new display module on the basic module Insert the switching module into the basic module Be sure to press evenly an...

Page 6: ...Fig 1 Step 3 Carefully lift the basic module up and out of the housing Be sure that at the lower section of the module the ribbon cable for connecting the sensor to a plug connector remains attached...

Page 7: ...module has been replaced the settings and programming for all modules are lost Transmit the previous settings to the instrument via PDM Note The default address is 126 It must be set to the previous a...