BA_060 Rev 1B6 Pressure transmitter PASCAL CS
Page 17/20
6.5.1
Configuring the output function (
out 1
/
2
)
You can choose a hysteresis or frame function as the output function. Furthermore you
can define whether the output is normally open or normally closed.
Display
Designation
Description
Hysteresis, normally open
If the pressure is above the switch-point the
switch is closed. At the lower range limit the
switch is open.
Hysteresis, normally
closed
If the pressure is above the switch-point is
open. At the lower range limit the switch is
closed.
Frame, normally open
Inside of the frame the switch is closed. At the
lower range limit the switch is open.
Frame, normally closed
Inside of the frame the switch is open. At the
lower range limit the switch is closed.
Return
Return to "
out 1
" or "
out 2
"
Table 13: Parameter list for output function
0
1
0
1
0
1
0
1
t
switch-point (
SP
) or
upper frame limit (
FH
)
reset-point (
rP
) or
lower frame limit (
FL
)
Hysteresis, normally open (
Hno
)
Hysteresis, normally closed (
Hnc
)
Frame, normally open (
Fno
)
Frame, normally closed (
Fnc
)
Figure 16: The output functions