  BA_005_2019-05_10.00  Pressure transmitter COMPACT 

Page 4/5 

 

4.1  Zero-point correction 

In the case of the field housing version, the potentiometers are encapsulated and can be 
accessed  through  the  clamping  plate.  In  the  case  of  plug  versions  and  the  cable-
connection version unscrew the union nut and remove the plug insert by carefully lifting it 
out.  The  internally-fitted  zero  and  span  potentiometers  can  be  accessed  from  above 
through the potting. Trim them using a screwdriver (1.5 x 40) (10 turns = ± 5 % of measur-
ing range). Span adjustment requires a precise reference pressure. 

  

 

Figure 2: Zero-point correction 

  

4.2  Devices with Diaphragm Seal 

Remove the protective cap or protective wrapping from the diaphragm only just before in-
stallation to prevent contamination or damage. 

The  diaphragm  must  not  be  touched.  Do  not  place  the  device  on  its  diaphragm.  Even 
small scratches or deformations may negatively influence the zero point or other charac-
teristics of the device. 

Pressure transmitter and diaphragm seal are a closed system that must not be separated. 

You  can  find  further  information  about  diaphragm  seals  in  the  document  TA_031  on 
www.labom.com.  

  

4.3  Maintenance / Service 

When  properly  installed  in  accordance  with  applicable  specifications,  this  device  is 
maintenance-free. However, we recommend an annual recalibration of the device. 

  

In  the event  of  any  damage or  defect  the  customer  cannot  replace  or  repair  any  compo-
nents or assemblies. 

  