BA_020_2019-05_10.00 Pressure transmitter UNIVERSAL
Page 3/5
3.1 Mechanical Installation
Before starting operation, check the process connection carefully for leaks under pressure.
Use gaskets, if required, that are suitable for the process connection and resistant to the
media.
You can use the device in any mounting position. Normally the transmitter is adjusted for a
vertical mounting position. A different mounting position in combination with a small nomi-
nal range might cause a zero point offset. In this case a zero point adjustment might be
necessary.
The device is ventilated via the connecting cable with a degree of IP67 protection and
pressure ranges up to 16 bar / 250 psi. During installation lay a ventilated cable to an
aeratable connection room. This compensates any atmospheric fluctuations.
3.2 Electrical Connection
Complete the mechanical installation before you connect the device electrically.
Set up all electrical connections while the voltage supply is switched off.
Figure 1: Options of the electrical connection
4
Operation
During operation, take care that the device remains within its intended pressure and tem-
perature ranges. No other monitoring is necessary.
The permissible ambient and media temperature depends on the type of device and its
design. This information can be found in the relevant data sheet.