Labkotec SET/V Operation And Installation Manual Download Page 4

SET/V  

D27093_e 

Operation and installation manual 

 

 

We reserve the right to any changes. 

 

Copyright © 2010, Labkotec Oy 

4(4)

 

5.  OPERATION TEST 

Always check the correct operation of the alarm 
after the installation and after making the 
connections. You should also check the operation 
every time the separator is emptied or at least 
once a year.

 

Testing the 
operation 

1.  The sensor is in the air. The 

device should be in normal mode 
(see chapter 4). 

 

2. Lower the sensing element of the 

sensor into the water or oil. The 
“Tank full” alarm should be issued 
(see chapter 4). 

 

3. Lift the sensor in the air. The 

alarm should stop after a while. 
Clean the sensor before installing 
it into the separator. 

If the sensor does not function as described, check 
the device settings from the control unit manual or 
contact the representative of the manufacturer.

6.  SERVICE AND REPAIR 

The sensor must be cleaned and tested when 
emptying the storage chamber and in connection 
with the annual maintenance. A mild detergent 
(e.g. washing-up liquid) and a scrubbing brush can 
be used for cleaning the sensor, if necessary.

 

 

During maintenance procedures (such as 
servicing the oil/fuel separator systems), the 
sensor should not be lifted out of the 
separator tank or installed back until there is 
water in the tank. 

 

 

 
The instructions concerning the inspection 
and maintenance of Ex equipment contained 
in standards IEC/EN 60079-17 and IEC/EN 
60079-19 should be observed when 
executing service, inspection, or repair 
procedures. 
  

                                    

 

 

Fault 
alarm 

The sensor is broken, there is a sensor 
cable break or a short circuit, or the 
sensor signal current is not recognized 
(digital system). 

 

The sensor circuit Fault indicator is on.  

 

The buzzer sounds  

 

The relays are de-energized. 

Figure 5. Installation example in an oil separator.

Summary of Contents for SET/V

Page 1: ... FI 33960 PIRKKALA Tel 358 029 006 260 Fax 358 029 006 1260 Internet www labkotec fi 18 5 2010 D27093_e We reserve the right to any changes Copyright 2010 Labkotec Oy 1 4 SET V High level sensor OPERATION AND INSTALLATION MANUAL ...

Page 2: ...g voltage Digital and analogical 7mA 13mA 8V 16V DC Cable Shielded oil proof cable 2 x 0 75 mm 2 Standard length 5 m Other lengths optional The max length of the fixed cable is 15 m Can be extended with a shielded cable The recommended maximum cable loop resistance is 75 Ω Materials PA PVC aluminum NBR Temperature range Operation 0 60 C Safety 30 60 C EMC Emissions EN 61000 6 3 Immunity EN 61000 6...

Page 3: ...are not exposed to strong stream flows mechanical abrasions or impacts The cable may be shortened or extended with a junction box if necessary The sensor is installed by hanging it from its cable at a suitable height so that the switch data is received as the surface level reaches the sensing element The example in figure 5 shows an oil separator application 4 OPERATION This chapter provides a gen...

Page 4: ... contact the representative of the manufacturer 6 SERVICE AND REPAIR The sensor must be cleaned and tested when emptying the storage chamber and in connection with the annual maintenance A mild detergent e g washing up liquid and a scrubbing brush can be used for cleaning the sensor if necessary During maintenance procedures such as servicing the oil fuel separator systems the sensor should not be...

Reviews: