Labkotec SET-1000 Installation And Operating Instructions Manual Download Page 8

SET-1000 

 

 

 

                                                          D15233FE-2 

Installation and Operating Instructions 

 

Copyright © 2019 Labkotec Oy 

8/14 

We reserve the right for changes without notice 

Normal situation 

When pressing the Test push button: 

 

 

 

Alarm and Fault LED indicators are immediately on. 

 

Buzzer is immediately on. 

 

Relays de-energize after 2 sec of continuous pressing. 

 

 

 

When the Test push button is released: 

 

 

 

LED indicators and buzzer go immediately off. 

 

Relays energize immediately. 

 

 

Alarm on 

When pressing the Test push button: 

 

 

 

Fault LED indicator is immediately on. 

 

Alarm LED indicator remains on. 

 

Buzzer remains on. If it has been reset earlier, it will return to be on. 

 

If relay 1 was already reset, it will de-energize again after 2 sec. of 
continuous pressing. 

 

Test will not affect relay 2, because it is already in alarm status. 

 

 

 

When the Test push button is released: 

 

 

 

The device returns without delay to the preceding status. 

 

 

Fault alarm on 

When pressing the Test push button: 

 

 

 

The device does not react to the test at all. 

 

3.2 

Altering settings 

If the default situation described above does not apply to the site being 
measured, the following device settings can be changed. 

Operating direction 

High level or low level function (increasing or decreasing level). 

Operation delay 

Two alternatives: 5 sec or 30 sec. 

Trigger level 

Trigger point of an alarm in the sensor

’s sensing element. 

Sensor selection 

Buzzer 

SET/DM3AL sensor or other Labkotec SET series sensor. 

The buzzer can be disabled. 

 

The  following  tasks  must  only  be  executed  by  a  person  with  proper 
education and knowledge of Ex-i devices. 

We recommend, that when altering the settings the mains voltage is off 
or the device is initialized before the installation is executed. 

 

 
Figure 9. Altering settings 

 

Summary of Contents for SET-1000

Page 1: ...NLAND Tel 358 29 006 260 Fax 358 29 006 1260 24 9 2019 Internet www labkotec fi D15233FE 2 1 14 Copyright 2019 Labkotec Oy We reserve the right for changes without notice SET 1000 Level switch for one...

Page 2: ...junction box 5 2 2 Cabling when using cable joint 6 3 OPERATION AND SETTINGS 7 3 1 Operation 7 3 2 Altering settings 8 4 TROUBLE SHOOTING 10 5 REPAIR AND SERVICE 11 6 SAFETY INSTRUCTIONS 11 APPENDICE...

Page 3: ...larms level control and alarms in oil sand and grease separators The LED indicators push buttons and interfaces of the device are described in figure 1 Figure 1 SET 1000 level switch features SET 1000...

Page 4: ...over The connectors of the external conductors are isolated by separating plates The plates must not be removed The plate covering the connectors must be installed back after executing cable connectio...

Page 5: ...equipotential ground thru the ground terminal Other components of the system that need to be grounded can also be connected to the same ground terminal The wire used for equipotential grounding must b...

Page 6: ...e between SET 1000 control unit and the sensor do not exceed the maximum allowed electrical parameters see appendix 1 Technical data IP rating of the cable joint is IP68 Make sure that the cable joint...

Page 7: ...representative of the manufacturer Normal mode no alarms The level in the tank is below the sensor Mains LED indicator is on Other LED indicators are off Relays 1 and 2 are energized High level alarm...

Page 8: ...is already in alarm status When the Test push button is released The device returns without delay to the preceding status Fault alarm on When pressing the Test push button The device does not react t...

Page 9: ...r s trigger level high level mode OPERATIONAL DELAY SETTING DELAY Switch S2 is used to set the operational delay of the device When the switch is in low position relays operate and buzzer is on after...

Page 10: ...e voltages should be between 10 3 11 8 V 3 If the voltages are correct measure the sensor current Do as follows 3 1 Disconnect sensor s wire from sensor connector pole 10 3 2 Measure short circuit cur...

Page 11: ...ional requirements and relevant standards as IEC EN 60079 25 and or IEC EN 60079 14 must be taken into account If electrostatic discharges can cause hazards in the operating environment the device mus...

Page 12: ...tential free relay outputs 250 V 5 A 100 VA Operational delay 5 sec or 30 sec Relays de energize at trigger point Operation mode selectable for increasing or decreasing level Electrical safety IEC EN...

Page 13: ...5 mH 0 5 mH 1 0 mH 2 0 mH 5 0 mH Lo Ro 116 5 H IIC and 466 H IIB Table 2 Electrical parameters Maximum length of the sensor cable is determined by the resistance max 75 and other electrical parameters...

Page 14: ......

Reviews: