Figure 37. Customer data
7.3.3.2. Inspection settings
In the Inspection settings menu, you can set the inspection period counter. You can select
between:
never (factory setting, inspection period not used)
1 month
3 months
6 months
12 months
Select the desired inspection period and press the Save button.
The selection (with the exception of "never") activates the inspection period counter, which
will activate the inspection alarm after the selected interval. The time of the maintenance is
shown in the home screen (year-month-day) and the control unit display (year-month).
The inspection counter can only be reset once the inspection alarm has been activated. In
other words, an inspection cannot be performed before the activation of the alarm (this does
not reset the counter).
Figure 38. Inspection settings
Installation and Operating Instructions | idOil-D30
35/51