background image

Pennant Pool Heater

Page 23

8.4 High Gas Consumption

Appliances operating with an improper air/fuel

ratio are very inefficient and consequently, have very
high gas consumption. Because efficiency is high
when the CO

2

 is high (or O

2

 is low), appliances

operating with low CO

2

 or high O

2

 (especially LP

appliances) consume more gas. Adjust the CO

2

 or O

2

for optimum efficiency. If no combustion analyzing
equipment (CO

2

 or O

2

) is available then a proper

adjustment of the air/fuel ratio (CO

2

 or O

2

) cannot be

accomplished. However, by briefly sniffing the flue
gases it is possible to determine if the CO

2

 or O

2

 is

within the proper range. No significant flue gas odor
should be detected when combustion is proper. A
strong piercing smell indicates poor combustion and
generally a lean mixture - low CO

2

 or high O

2

 

. The

CO

2

 should be 8% (natural gas, 9.2% LP) at high fire.

To check the CO

2

, first verify that the supply gas

pressure is within 5" to 13" w.c. (1.2 to 3.2 kPa) With
the Pennant running with both stages firing, set the air
box pressure to 1.5" w.c. (0.37 kPa) (as a starting
point), by adjusting the air shutter(s) at the bottom of
the fan(s). Check the CO

2

, and adjust the air shutters if

further adjustment to the CO

2

 is needed. Sizess 1250,

1500, 1750 and 2000 have two blowers and two air
chambers (boxes). The pressure of each air box must
be equal when the final adjustment is made.

8.5 Troubleshooting the Pool Heater

Temperature Control

With a Voltmeter, test for 24 VAC between

terminals 1 & 2 on the 10 pin connector. Check that
the sensor temperature is lower than the setpoint
temperature by at least the differential setting. If this is
true, check that there is 24 VAC at the yellow wire on
the 4 pin connector. If there is not 24 VAC, check that
the high limit is not open. If there is 24 VAC at the
yellow wire on the 4 pin connector and not at the light
blue wire on that connector, replace the control.

8.6 Troubleshooting Pennant Controls

The Pennant series consists of three sizes with

one ignition module (500, 750 & 1000) and four sizess
with two ignition modules (1250, 1500, 1750 and
2000).

A diagnostic panel, that includes test points, as well

as diagnostic lights, is provided in the control module. It
is located on the right side of the module, behind the
display. To access, remove the retaining screws from the
display cover panel and remove it. Grasp the control
module at its base and pull it outward. Ladder diagrams
are shown in Figures 13 and 14.

Figure 13 shows the diagram for the 500, 750 &

1000. These have one blower and one ignition module.
The blower is energized directly through the “inducer”
terminals F1 and F2 of the (Fenwal) ignition module. The
24V power to the T’STAT terminal of the ignition
module(s) are routed through the safety interlocks.

The ladder diagram for sizess 1250, 1500, 1750

and 2000 is shown in Figure 14. These models have
two ignition modules, each with its own blower, and
each controlling part of the input so that startup at
reduced input is provided. The blowers are energized
by the ignition modules indirectly via switching
relays. When either ignition module receives a call for
heat, it switches its blower to high speed and the
blower of the idle ignition module to low speed.

The wiring schematic for the Pennant 500 – 1000

is shown in Figure 15, and the schematic for the 1250
– 2000 models is shown in Figures 16 and 17. All 24V
wiring is routed through the diagnostic PC board.
Wiring harnesses connect between the diagnostic PC
board and the control components, indicator board, or
field wiring terminal strip. The diagnostic board
contains LEDs that indicate open status of the safety
interlocks, and quick-connect terminals that provide
tests points for checking voltage/continuity at various
points in the control circuit.

Certain control elements that may need to be

rewired in the field are connected via the field wiring
terminal strip rather than to the diagnostic PC board.
These include the low-water cutoff (LWCO), external
alarm, and water flow switch.

SECTION 9.
Replacement Parts

Only genuine Laars replacement parts should be used.

9.1 General Information

To order or purchase parts for the Laars Pennant,

contact your nearest Laars dealer or distributor. If they
cannot supply you with what you need, contact
Customer Service (see back cover for address,
telephone and fax numbers).

9.2 Parts List

See next page.

Summary of Contents for PNCP

Page 1: ...ualified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or deat...

Page 2: ...ntrol 14 5 3 1 Temperature Control Overview 14 5 3 2 Programming Control Parameters 14 5 3 3 Setpoint LSP 15 5 3 4 Differential dLS 16 5 3 5 Pump Operation 16 5 3 6 Heater Purge Pump Delay PD 16 5 4 L...

Page 3: ...oper installation The Pennant appliance is protected against over pressurization A pressure relief valve is fitted to all appliances It is installed on the outlet header at the water outlet of the app...

Page 4: ...of the structure When such a location is not available it is recommended that a suitable drain pan adequately drained be installed under the appliance The appliance is design certified by CSA Interna...

Page 5: ...86 101 8 26 30 78 29 75 8 22 8 22 80 203 8 20 12 30 8 20 1500 78 199 39 101 101 8 26 30 78 29 75 8 22 8 22 91 231 8 20 12 30 8 20 1750 89 226 44 113 101 8 26 30 78 29 75 8 22 8 22 101 256 8 20 14 36...

Page 6: ...stion Air From Room In the United States the most common requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2 which follow Where ducts are used they...

Page 7: ...d pipe per table 4 for the combustion air intake see Table 1 for appropriate size Route the intake to the heater as directly as possible Seal all joints with tape Provide adequate hangers The unit mus...

Page 8: ...to excessive stack spill or backpressure indicating a blocked vent condition that all appliances attached to the vent be locked out and prevented from operating Note that the Pennant Pool Heater is e...

Page 9: ...al so the vent exhaust does not settle on building surfaces and other nearby objects Vent products may damage such surfaces or objects 6 Locate the terminal at least 6 feet 1 8m horizontally from any...

Page 10: ...3 4 Vertical Combustion Air Terminal When combustion air is taken from the roof a field supplied rain cap or an elbow arrangement must be used to prevent entry of rain water see Figure 2 The opening...

Page 11: ...gas by checking the rating plate Laars Heating Systems appliances are normally equipped to operate at elevations up to 2000 feet 610m Pennant appliances may be adjusted to operate properly at higher e...

Page 12: ...are installed Maintain 1 clearance to combustibles for hot water pipes Pipe the discharge of the relief valve full size to a drain or in a manner to prevent injury in the event of pressure relief Inst...

Page 13: ...e latest edition of the National Electrical Code ANSI NFPA 70 in the U S and with latest edition of CSA C22 1 Canadian Electrical Code Part 1 in Canada Do not rely on the gas or water piping to ground...

Page 14: ...exchanger to prevent damage from condensation The sensors for the control are installed as shown in Figure 6 and Section 4 3 Sensor Locations The automatic mixing system sensor already installed is sh...

Page 15: ...15 15 750 20 15 15 1000 20 20 15 1250 30 25 15 1500 30 25 15 1750 25 20 2000 25 20 Table 8 Electrical Data Amps Figure 9 Typical Control Panel Figure 8 Pool Heater Controller The last parameter that m...

Page 16: ...up to three times only once if optional lockout ignition module is used Loss of flame signal from the first ignition module will cause shutdown of the heater When the call for heat is satisfied the g...

Page 17: ...roblems such as failure to start rough ignition strong exhaust odors etc can be due to improper setup Damage to the heater resulting from improper setup is not covered by the limited warranty 1 Using...

Page 18: ...t this process until all gas valves have been set Note The pressure can be set only when the appliance is operating and only when the particular gas valve being adjusted is energized by a call for hea...

Page 19: ...go through a prepurge period and ignitor warm up period followed by ignition 6 9 Therapeutic Pools Spas Therapeutic pools or spa pools are usually piped and controlled so that very warm or hot water o...

Page 20: ...rough the ignitor hole s using a flashlight to illuminate If there is any indication of debris on the burners that are visible all the burners will need to be inspected more thoroughly Remove the scre...

Page 21: ...mer is not capable of supplying control voltage for external devices Should a transformer need replacing shut off the 120 volt power Unplug the transformer wires remove the mounting screws and remove...

Page 22: ...e inspected There should be no distortion or perforations in the burners outside of the active burner port area Replace if indicated 8 3 Short Cycling Because of the large mass of pool systems short c...

Page 23: ...and 2000 A diagnostic panel that includes test points as well as diagnostic lights is provided in the control module It is located on the right side of the module behind the display To access remove t...

Page 24: ...5C3502 5C3502 5C3502 5C3502 5C3502 5C3502 11 Plate Vent 5C3004 10C3004 10C3004 20C3004 20C3004 20C3004 20C3004 12 Cover Vent Plate 20C3006 20C3006 20C3006 20C3006 13 Plate Cover Filter 5C3002 5C3002...

Page 25: ...2004 12C2010 15C2004 17C2010 20C2010 29 Door Chamber Access 5C2005 5C2005 5C2005 5C2005 5C2005 5C2005 5C2005 1 1 1 2 2 2 2 30 Cover Chamber Front Right 12C2008 15C2004 17C2008 20C2008 Gasket Tape Rear...

Page 26: ...64501 10364501 10364501 46 Well Temperature Control RE2058300 RE2058300 RE2058300 RE2058300 RE2058300 RE2058300 RE2058300 47 Gasket Flange S0063700 S0063700 S0063700 S0063700 S0063700 S0063700 S006370...

Page 27: ...ltion Control 3 Try non CSD 1 E2313900 E2313900 E2313900 E2313900 E2313900 E2313900 E2313900 1 1 2 2 2 2 2 67 Diagnostic Board E2105500 E2105500 E2105500 E2105500 E2105500 E2105500 E2105500 68 Indicat...

Page 28: ...t 10C6500 10C6500 10C6500 10C6500 2 2 2 4 Burner Manifold Assy 3 Burners Right LP 5C6620 5C6620 5C6620 5C6620 5C6620 1 1 2 1 1 Burner Manifold Assy 3 Burners Left LP 5C6520 5C6520 5C6520 5C6520 5C6500...

Page 29: ...00 L2012600 L2012600 L2012600 2 2 2 4 82 Burner Tray 3 Burners L2012200 L2012200 L2012200 L2012200 L2012200 2 3 5 2 3 Burner Tray 4 Burners L2012500 L2012500 L2012500 L2012500 3 3 3 6 82A Gasket Burne...

Page 30: ...LAARS Heating Systems Page 30 Figure 10 Sheet Metal Components...

Page 31: ...Pennant Pool Heater Page 31 Figure 11 Internal Components...

Page 32: ...LAARS Heating Systems Page 32 Figure 12 Heat Exchanger Components A Enlargement from previous page...

Page 33: ...Pennant Pool Heater Page 33 Figure 13 Pennant 500 1000 Ladder Diagram SECTION 10 Wiring Diagrams...

Page 34: ...LAARS Heating Systems Page 34 Figure 14 Pennant 1250 2000 Ladder Diagram...

Page 35: ...Pennant Pool Heater Page 35 Figure 15 Pennant 500 1000 Wiring Schematic...

Page 36: ...LAARS Heating Systems Page 36 Figure 16 Pennant 1250 1500 Wiring Schematic...

Page 37: ...Pennant Pool Heater Page 37 Figure 17 Pennant 1750 2000 Wiring Schematic...

Page 38: ...LAARS Heating Systems Page 38 Figure 18 Field Wiring...

Page 39: ...Pennant Pool Heater Page 39...

Page 40: ...335 6300 Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1201 Document 3...

Reviews: