101
Service Manual - NeoTherm 500
Appendix 1 - Error Codes (continued)
Code Description
L or H
Procedure
210
Invalid postpurge time setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
211
Invalid power up with lockout setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
212
Invalid preignition time setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
213
Invalid prepurge rate setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
214
Invalid prepurge time setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
215
Invalid purge rate proving setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
216
Invalid run flame failure response setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
217
Invalid run stabilization time setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
218
Invalid stack limit enable setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
219
Invalid stack limit response setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
220
Unconfigured Delta T limit setpoint setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
App1
cont.
Summary of Contents for NeoThem NTH
Page 2: ......
Page 10: ...Service Manual NeoTherm 500 viii ...
Page 68: ...58 Service Manual NeoTherm 500 ...
Page 115: ...105 Service Manual NeoTherm 500 Appendix 3 Wiring Diagram App3 ...
Page 116: ...106 Service Manual NeoTherm 500 ...
Page 117: ......