Mighty Therm
2
Page 5
or combustion air terminal terminate through a wall,
and there is potential for snow accumulation in the local
area, both terminals should be installed at an appropriate
level above grade.
The dimensions and requirements that are shown in
Table 1
should be met when choosing the locations for
the appliance.
1.6 Locating Pump-Mounted Water Heater
with Respect to Storage Tank(s)
For best results, a pump-mounted Mighty Therm2
water heater should be located within 15 feet (4.6m) of
the storage tank(s). The pump is sized for 30 feet (9.1m)
of piping.
If the appliance must be installed with longer
piping runs, then larger diameter pipe or tubing shall be
used. Consult the factory for assistance.
Figure 1. Dimensional Data (standard units).
Air
Vent
Shipping Weight
1
Unit
Conn.
Conn.
Size
A
B
C
D
E
W
V
lbs
kg
500
33¾
85
16¾
43
6½
17
10
25
8
20
6
15
8
20
425
193
750
45¾
116
22¾
53
6½
17
10
25
9½
24
8
20
10
25
505
229
1000
57¾
147
28¾
73
6½
17
10
25
9½
24
8
20
10
25
615
279
1250
68¼
173
34
87
10¼
26
10
25
9
23
12
30
12
30
675
306
1500
78¾
200
39½
100
10¼
26
10
25
9
23
12
30
12
30
760
345
1750
89¼
227
44¾
113
10¼
26
10
25
9
23
12
30
14
36
825
375
2000
99¾
253
49¾
127
10¼
26
10
25
9
23
12
30
14
36
955
434
NOTES:
1. Add 55 lbs (25kg) for pump-mounted units.
Dimensions in inches
cm.
Summary of Contents for MIGHTY THERM2
Page 23: ...Mighty Therm2 Page 23 Figure 19 Mighty Therm2 500 750 Connection Diagram...
Page 24: ...LAARS Heating Systems Page 24 Figure 20 Mighty Therm2 1000 Connection Diagram...
Page 37: ...Mighty Therm2 Page 37 Figure 23 Sheet Metal Components 12A 12B 12C...
Page 38: ...LAARS Heating Systems Page 38 Figure 24 Internal Components...