The FT Series, Heating Only, Gas Conversion Kit
pg 3 of 4
Figure C
Table B
DIP Switch Settings
MBH 80 100 120 140 N/A 199
9.
Per
Table B
, set DIP Switch
5 to OFF
for LP Propane.
10.
Turn
ON
the GAS and WATER supply to the FT.
11.
Turn
ON
the FT.
12.
Connect a manometer to the manifold pressure port. For dual port manometers, use the positive pressure
side. Check for proper manifold gas pressure. Refer to Table C.
ON
OFF
MIN
Fire
Normal Operation
MAX
Fire
Normal Operation
NG Natural
LP Propane
3” Vent Size
2” Vent Size
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
ON
Figure D
Gas Valve for
80 to 140 MBH
Gas Valve for
199 MBH
The gas valve on
the smaller models is
mounted vertically.
Manifold Pressure Port
Manifold Pressure Port
DO
N
OT
C H
A N
G E
REFE
RENCE
ON
LY.
Table C
Manifold pressure
Propane Gas (LP)
Natural Gas (NG)
MFTHW
80/100
-0.102
˝
WC
-0.102
˝
WC
0.00
˝
WC
0.00
˝
WC
MFTHW
120/140
-0.216
˝
WC
-0.216
˝
WC
0.00
˝
WC
0.00
˝
WC
MFTHW
175
-0.169
˝
WC
-0.129
˝
WC
-0.015
˝
WC
-0.015
˝
WC
MFTHW
199
-0.173WC
-0.134
˝
WC
-0.015
˝
WC
-0.015
˝
WC
CO
2
value
Propane Gas (LP)
Natural Gas (NG)
2˝ VENT
3˝ VENT
2˝ VENT
3˝ VENT
MFTHW
80/100
120/140/175/199
9.5~11%
8.5~10.5%
9~10.5 %
8~10%
Refer to the below table.
Manifold pressure
Propane Gas (LP)
Natural Gas (NG)
MFTHW
80/100
-0.102
˝
WC
-0.102
˝
WC
0.00
˝
WC
0.00
˝
WC
MFTHW
120/140
-0.216
˝
WC
-0.216
˝
WC
0.00
˝
WC
0.00
˝
WC
MFTHW
175
-0.169
˝
WC
-0.129
˝
WC
-0.015
˝
WC
-0.015
˝
WC
MFTHW
199
-0.173WC
-0.134
˝
WC
-0.015
˝
WC
-0.015
˝
WC
CO
2
value
Propane Gas (LP)
Natural Gas (NG)
2˝ VENT
3˝ VENT
2˝ VENT
3˝ VENT
MFTHW
80/100
120/140/175/199
9.5~11%
8.5~10.5%
9~10.5 %
8~10%
Refer to the below table.
13.
Establish a call for heat. You may need to disconnect the outdoor reset if you are making this gas
conversion during warm weather.
For details, reference Section 4.18 or 4.19 of
your Installation and Operating Manual.
Shown in this example are the DIP switch settings
for a model 140 using Natural Gas and 3” Venting
and in Normal Operation.
175
Summary of Contents for Mascot FT COMBI-WALL
Page 4: ...Page 4 LAARS Heating Systems COMBI MODELS ONLY ...
Page 5: ...Page 5 MASCOT FT COMBI MODELS ONLY ...
Page 7: ...Page 7 MASCOT FT To exit at the end of any step press the Mode button HEATING ONLY MODELS ...
Page 8: ...Page 8 LAARS Heating Systems HEATING ONLY MODELS ...
Page 9: ...Page 9 MASCOT FT HEATING ONLY MODELS ...
Page 11: ...Page 11 MASCOT FT To exit at the end of any step press the Mode button HEATING ONLY MODELS ...
Page 13: ...Page 13 MASCOT FT COMBI AND HEATING ONLY MODELS ...
Page 14: ...Page 14 LAARS Heating Systems This page intentionally left blank ...
Page 15: ...Page 15 MASCOT FT This page intentionally left blank ...