The FT Series Wall Mounted, Combination Boiler
Page 45
4.17
Disposal of Condensate
1
2
3
4
Condensate
drain pipe
(View is as if side panel
were removed)
Condensate
Trap
High efficiency gas condensing Boilers create
condensation when operating. Condensation has
acidic (pH) of approximately 4-5.
Condensate must be drained in accordance with all
local regulations. Follow your local code with regards
to the disposal of condensation.
One of 4 disposal methods must be followed
1. to floor drain
2. to neutralizer (optional kit)
3. to laundry tub
4. to condensate pump (field supplied)
If a neutralizer is installed, periodic replacement of the
lime stone (or neutralizing agent) will be required. The
rate of depletion of the lime stone varies upon usage
of the boiler. During the first year of operation, please
check the neutralizer every few months for depletion.
Apply only corrosion-resistant materials for the
condensate drain lines such as 1/2˝ PVC, CPVC,
Polypropylene pipe or included plastic hose.
NOTICE
Category II & IV water heaters must be installed with a
means provided for the drainage of condensate.
AVIS
Catégorie II & ; IV chauffe-eau doit être installé
avec une moyens prévus pour l’évacuation des
condensats.
CAUTION
Condensate is mildly acidic (pH=5), and may harm
some floor drains and/or pipes, particularly those
that are metal. Ensure that the drain, drainpipe, and
anything that will come in contact with the condensate
can withstand the acidity, or neutralize the condensate
before disposal.
Damage caused by failure to install
a neutralizer kit or to adequately treat condensate
will not be the manufacturer’s responsibility.
Contact Manufacturer to order
Neutralizer Kit# A2123601
_________________________________________
Summary of Contents for FT Series
Page 50: ...Page 50 4 22 Ladder Diagram F B level Air Pressure Sensor...
Page 66: ...Page 66 6 2 Fault Tree Analysis 1 Flame detection...
Page 81: ...Mascot FT Combination Boiler Page 81 Heat Exchanger Tank _ Feature Heat Exchanger Tank FTCW140...
Page 83: ...Mascot FT Combination Boiler Page 83 Fan Gas Valve _ Feature Blower and Gas Valve FTCW140...
Page 85: ...The FT Series Wall Mounted Combination Boiler Page 85 FTCW199...