DuraFlow Water Heater

Page 5

Figure 5. Internal View of Remote Bulb Aquastat
Controller.

1C. Wiring

Wire relay (see Figure 4) to reverse acting

aquastat (supplied) to start boiler and system pump.

For maximum domestic water capacity, aquastat must

be wired in priority (as shown) or utilize multiple zone

relay with priority.

Figure 6. Mounting the Boiler Fitting.

SECTION 2.
Remote Bulb Aquastat Controller

2A. Application

This remote bulb, immersion-type controller

operates in response to temperature changes in

hydronic heating systems and in other heated liquids.

It provides spdt switching for three wire circuit

applications, combining low limit and circulator

control.

Switch ratings are shown on the inside cover.

The electrical requirements of controlled equipment

must not exceed these ratings.

The R to B contacts make to start the boiler when

the boiler water temperature drops to the dial setting

less the differential. The R to W contact breaks to

prevent circulator operation. When the boiler water

temperature rises to the dial setting, R to B breaks and

R to W makes (see Figure 5).

2B. Installation

WARNING

CAN CAUSE PROPERTY DAMAGE, SEVERE
INJURY OR DEATH. This product is intended for
use only in systems with a pressure relief valve.

Caution

Disconnect the power supply before beginning
installation to prevent electrical shock or equipment
damage.

2B-1. Mounting with Boiler Fitting

1.

Screw the fitting into the boiler or pipe

tapping.

2.

Place the packing nut on the tubing.

3.

Slide the bulb completely through the

fitting to bottom third of tank.

4.

Place the composition disk and four slotted

brass washers on the tubing in the order

shown in Figure 6. Turn brass washers so

that the slots are 180 degrees to each other.

5.

Slide the seal assembly into the fitting and

tighten the packing nut.

2B-2. Wiring

Be sure all wiring agrees with applicable codes,

ordinances, and regulations for wire size, type of

insulation, and enclosure. The controllers are provided

with conduit knock-outs in the top and bottom of case.

Refer to Figure 7 for typical connection diagram.

OUT OF

PRODUCTION

Summary of Contents for duraflow

Page 1: ...Installation and Operation Instructions Document 2110A Installation and Operation Instructions for DuraFlow Water Heater 2400 382A A subsidiary of BRADFORD WHITE Corporation OUT OF PRODUCTION...

Page 2: ...NTS SECTION 1 General Information 1A Introduction 3 1B Piping 3 1C Wiring 5 SECTION 2 Remote Bulb Aquastat Controller 2A Application 5 2B Installation 5 2B 1 Mounting with Boiler Fitting 5 2B 2 Wiring...

Page 3: ...and buffer applications the DuraFlow must always be piped with a thermally trapped tempering valve and flow restrictor set for applicable boiler input When utilized as both a buffer and a domestic wa...

Page 4: ...TRANSFORMER DISCONNECT SWITCH L2 L1 LOW MASS BOILER TERMINALS DURAFLOW WATER HEATER AQUASTAT ZONE THERMOSTATS ZONE VALVES NO NC C RELAY G L1 L2 T T Figure 3 Piped as Buffer and Indirect NOTE Pump Ope...

Page 5: ...breaks to prevent circulator operation When the boiler water temperature rises to the dial setting R to B breaks and R to W makes see Figure 5 2B Installation WARNING CAN CAUSE PROPERTY DAMAGE SEVERE...

Page 6: ...with the boiler manufacturer s recommendations To adjust insert a screwdriver in the slotted screw type head located beneath the window in the cover Turn the scale to the desired control point 2D Chec...

Page 7: ...DuraFlow Water Heater Page 7 OUT OF PRODUCTION...

Page 8: ...s All of above Part A plus Insulation and mechanical components furnished to Laars by other manufacturers such as pumps relays controls gauges etc Such components may carry warranties from their respe...

Reviews: