7.  CIRCULATION PUMP

 : . It would be better to install it on the return in order to avoid that it could disconnect itself at very high water 

temperatures but checking that it does not drive water in the open expansion tank otherwise it should cause a continuous water 

oxygenation with consequent, fast corrosion of boiler body. It must be not to avoid a forced circulation in the open expansion tank. 

Furthermore it must be electrically connected to a thermostat or a electronic control unit that can be purchased with the thermo-

fireplace as 

OPTIONAL

 part.

8.  AUTOMATIC THERMOSTATIC MIXING VALVE

 – (see chapter 

2.3

)

IMPORTANT

: temperature safety sensors must be in place on the machine or at a distance no greater than 30 cm from the flow connection 

of the thermo-product. Whenever the thermo products lack a device, those missing can be installed on the thermo product flow pipe, 

within a distance no greater than 1m from the thermo product.

ATTENTION

For no reason must the fire be ignited before the system has been completely filled with water; doing this would 

lead to serious damage of the entire structure

. The system must be filled by means of the loading pipe directly from the open tank 

in a way to prevent an excessive pressure  of the water network deforming the body of the thermo heating stove.

The system must be kept constantly full of water even during the periods when the use of the thermo-heating stove is not requested. During 

the winter, inactivity must be faced with the addition of antifreeze.

2.2.  CLOSED expansion Tank system

It is 

COMPULSORY

 that the CLOSED expansion Tank system is provided with:

1.  A 3 bar SAFETY VALVE

:   maximum operation pressure allowed for the system is 3 bar (equal to 30 m of the water column). Higher 

pressures can cause deformation and breakage of the boiler body 

2.  AUTOMATIC THERMOSTATIC MIXING VALVE

 – (see chapter 

2.3

)

3.  HEAT DISCHARGE VALVE

 or 

HEAT SAFETY DISCHARGE

 (positive safety, therefore, this continues discharge, should the valve 

be damaged)

4.  CLOSED EXPANSION Tank
5.  PUMP CONTROL THERMOSTAT
6.  NOISE ALARM ACTIVATION THERMOSTAT
7.  NOISE ALARM
8.  TEMPERATURE INDICATOR
9.  PRESSURE INDICATOR
10.  PUMP SYSTEM

IMPORTANT

: temperature safety sensors must be in place on the machine at a distance no greater than 30 cm from the flow connection 

of the thermo-product. Whenever the thermo products lack a device, those missing can be installed on the thermo product flow pipe, 

within a distance no greater than 1m from the thermo product.

IT IS MA NDATORY

 that the thermo products for domestic heating inserted in 

CLOSED Tank

 heating systems, must be internally equipped, 

with a cooling circuit, prepared by the unit manufacturer, which is activated by a thermal 

safety valve

 (see chapter 

2.4

) which does not 

require auxiliary power and can guarantee that the standard set temperature limit is not exceeded.  Connection between the power supply 

unit and the valve must be free from interceptions. Cooling circuit upstream pressure must be at least 1,5 bar.

2.3.  AUTOMATIC THERMOSTATIC MIXER VALVE - (OPTIONAL)

The automatic thermostatic mixer valve finds applications in solid fuel heat generators as it prevents cold water return in the exchanger.

Picture 1 at page 46

 

Routes 

1

 and 

3

 are always open and, along with the pump installed on the return (

R

), they guarantee water circulation inside the biomass 

boiler exchanger (

CB

). An elevated return temperature, allows efficiency improvement, reduces formation of smoke condensation and 

prolongs the boiler life span. 

Valves on the market have different calibrations. NORDICA advises use of model 55°c with 1” hydraulic connections. Once the valve 

calibration temperature is reached, route 

2

 opens and the boiler water goes to the system via the flow (

M

).

IMPORTANT lack of installation of the device voids the heat exchanger warranty.

2.4.  HEAT DISCHARGE VALVE - (OPTIONAL) 

Solid fuel thermo products must be installed with safety devices determined by laws in vigour.

For this reason the thermo products is equipped with a heat discharge coil. (see Pos.6 chapter 

13 at page 47

)

The heat discharge coil must have one side connected to the water network (

A

) and the other rot drainage network (

C

). When the safety 

temperature is reached, the heat discharge valve, the bulb of which is to be connected to attachment

 B

, enables the intake of cold water 

in the boiler coil, discharging the excess heat out of pipe 

C

 towards a conveniently installed drain.

Cooling circuit upstream pressure must be at least 1,5 bar.

2.5.  SYSTEM CONNECTION AND FILLING

Some examples, purely indicative of the installation, are reported at chapter 

12

, while the connections to the thermoproduct are reported 

at chapter 

13

.

ATTENTION: The filling of the system must take place exclusively by the natural fall of the water from the open expansion tank 

through the feed pipe in order to avoid that a too high water system grid pressure could change or cause the explosion of 

boiler body

.

Summary of Contents for FLY IDRO DSA

Page 1: ...achten ist es notwendig unsere Produkte vorsichtig nach den in diesem Handbuch enthaltenen Anweisungen zu installieren und anzuwenden R GL S DE S CURIT SUR LES APPAREILS Selon les normes de s curit su...

Page 2: ......

Page 3: ...rials which will get in touch with food are suitable for alimentary use according to the a m CE regulation KONFORMIT TSERKL RUNG DES HERSTELLERS Betreff Fehlen von Asbest und Kadmium Wir best tigen da...

Page 4: ...FLY IDRO DSA 4 7193505 IT EN DE FR...

Page 5: ...HERMOK CHE INSTALLATION SCHEME 41 13 SCHEDE TECNICHE TECHNICAL DATA SHEETS TECHNISCHE PROTOKOLLE FICHES TECHNIQUES 46 14 MONTAGGIO ASSEMBLY MONTAGE 49 EN CONTENTS 1 GENERAL PRECAUTIONS 15 2 INSTALLATI...

Page 6: ...LAY OUT ALLGEMEINES INSTALLATIONSSCHEMA THERMOK CHE INSTALLATION SCHEME 41 13 SCHEDE TECNICHE TECHNICAL DATA SHEETS TECHNISCHE PROTOKOLLE FICHES TECHNIQUES 46 14 MONTAGGIO ASSEMBLY MONTAGE 49 DE INHAL...

Page 7: ...so sia costruito in materiale infiammabile assicurarsi che nella stanza dove sar installato vi sia una ventilazione adeguata presenza di presa d aria vedi capitolo 6 evitare l installazione in locali...

Page 8: ...TORE 6 TERMOSTATO DI ATTIVAZIONE DELL ALLARME ACUSTICO 7 ALLARME ACUSTICO 8 INDICATORE DI TEMPERATURA 9 INDICATORE DI PRESSIONE 10 SISTEMA DI CIRCOLAZIONE IMPORTANTE i sensori di sicurezza della tempe...

Page 9: ...eriale non infiammabile ad esempio ceramica pietra vetro o acciaio etc dimensioni secondo l ordinamento regionale Il sottofondo deve sporgere frontalmente di almeno 50 cm e lateralmente di almeno altr...

Page 10: ...8h la capacit di riscaldamento diminuisce del 25 circa 5 CANNA FUMARIA Requisiti fondamentali per un corretto funzionamento dell apparecchio la sezione interna deve essere preferibilmente circolare es...

Page 11: ...0683 2005 ITALIA prevede che le curve o variazioni di direzione non devono in nessun caso essere superiori a 2 compresa l immissione in canna fumaria Volendo usare la canna fumaria di un caminetto o f...

Page 12: ...ll installazione del rivestimento estetico e dell accensione del termoprodotto bisogna riempire per naturale caduta dell acqua l impianto ed il termoprodotto tramite il vaso di espansione aperto vedi...

Page 13: ...i all eccessivo surriscaldamento effetto forgia in caso contrario decade la garanzia Con i registri posti sulla facciata dell apparecchio viene regolata l emissione di calore dello stesso Essi devono...

Page 14: ...ato nel tempo l aspetto estetico con della vaselina neutra Verificare il livello dell acqua del vaso di espansione e fare uscire l eventuale aria dell impianto sfiatando i radiatori verificare inoltre...

Page 15: ...fino allo spegnimento e raffreddamento completo delle ceneri 10 4 MANUTENZIONE DELL IMPIANTO IDRAULICO Ad impianto spento una volta all anno eseguire le seguenti verifiche controllare la funzionalit...

Page 16: ...ight of the appliance and if it is made of flammable material provide suitable insulation Make sure that there is adequate ventilation by means of an air intake see chapter 6 in the room where the app...

Page 17: ...a device those missing can be installed on the thermo product flow pipe within a distance no greater than 1m from the thermo product IT IS MANDATORY that the thermo products for domestic heating inse...

Page 18: ...s heat resistant gloves control devices Make sure that children are aware of these dangers and keep them away from the fireplace while functioning The use of a wrong or wet fuel causes the formation o...

Page 19: ...section of the flue be built so as to prevent rain snow or any foreign body entering the flue be easy to inspect for any maintenance and cleaning operations 5 2 CONNECTION TO THE CHIMNEY Products with...

Page 20: ...y essential that in environments in which thermo products are operated with a natural chimney draught as much air as is necessary for combustion is introduced i e up to 25 m hour The natural recircula...

Page 21: ...ls and paints to complete the various elastic stresses in detail initially it is possible to remark the emission of smells typical of metals subject to great thermal stress as well as of wet paint Thi...

Page 22: ...stion Then load a reduced quantity of fuel in order to permit a rapid burning growing up of the flames and the stabilization of the draught Then check that all openings for the cleaning and the connec...

Page 23: ...eat shock of 750 C they are not subject to thermal shocks Their break can be caused only by mechanic shocks bumps or violent closure of the door etc Therefore their replacement is not included in the...

Page 24: ...einfeger ist von der Installation des Heizungsherds zu unterrichten damit er seinen ordnungsgem en Anschluss an den Rauchabzug und dessen Leistungsverm gen berpr fen kann Vor der Installation folgende...

Page 25: ...sein 1 SICHERHEITSVENTIL von 3 bar Der h chstzul ssige Betriebsdruck f r die Anlage bel uft sich auf 3 bar entspricht einer Wassers ule von 30 m h here Dr cke k nnen Verformungen und ein Bersten des K...

Page 26: ...werden Fu b den aus brennbaren Materialien wie Teppich Parkett oder Kork m ssen durch einen entsprechenden Belag aus nicht brennbaren Baustoffen zum Beispiel Keramik Stein Glas oder Stahl ersetzt wer...

Page 27: ...lte vorzugsweise kreisf rmig sein Er muss w rmeisoliert und wasserundurchl ssig und mit Materialien gebaut sein die der Hitze den Verbrennungsprodukten und eventuellen Kondensaten widerstehen Er darf...

Page 28: ...heblich was gegebenenfalls durch dessen angemessene Erh hung des Rauchabzugs auszugleichen ist Die Norm UNI 10683 2005 ITALIA sieht vor dass es in keinem Fall mehr als 2 B gen oder Richtungs nderungen...

Page 29: ...ACHTUNG Man darf das Feuer keinesfalls anz nden wenn die Anlage nicht mit Wasser gef llt wurde sollte man dies dennoch tun k nnte dadurch die gesamte Anlage besch digt werden BEI VOLLST NDIGEM ODER T...

Page 30: ...enn man sicher ist dass das Ger t korrekt funktioniert WARNUNG Bei der Konstruktion der Auskleidung muss man eventuelle sp tere Wartung der installierten elektrischen Komponenten z B Gebl se Temperatu...

Page 31: ...ollte diese nicht perfekt abdichten dass hei t liegen diese nicht mehr an der T re an kann die Funktionst chtigkeit des Ger tes nicht garantiert werden Folglich m ssen sie ersetzt werden Im Falle von...

Page 32: ...ntfernten Aschen sind in einem Beh lter aus feuerfestem Material mit einem dichten Deckel aufzubewahren Der Beh lter ist auf einem feuerfesten Boden weit von brennbaren Stoffen bis zur vollkommenen L...

Page 33: ...i ces de rechange non originales Le ramoneur habituel de votre zone doit tre inform de la mise en place de la cuisini re thermique pour qu il puisse en contr ler la juste connexion au conduit de fum e...

Page 34: ...n excessive du r seau hydrique d forme la structure de la thermo chaudi re L installation doit tre constamment pleine d eau m me quand la thermo chaudi re est inutilis e En hiver l ventuelle inutilisa...

Page 35: ...s curit sont indiqu es dans l tiquette du produit et on il NE FAUT PAS descendre au dessous des valeurs indiqu s b devant la porte du foyer dans la zone de radiation de cette derni re il ne doit y av...

Page 36: ...les isolations thermiques est de 30 Kcal h x m3 type de construction favorable 441 m 40 Kcal h x m3 type de construction moins favorable 331 m 50 Kcal h x m3 type de construction d favorable 264 m Ave...

Page 37: ...ompens e par un exhaussement du conduit de fum e la partie horizontale ne devra jamais d passer en tout cas 2 m UNI 10683 2005 chaque courbe du canal des fum es r duit sensiblement le tirage du condui...

Page 38: ...tol myrte etc on cause rapidement des d g ts clivage au niveau des l ments en fonte du produit 8 ALLUMAGE ATTENTION En aucun cas il ne faut allumer le feu avant que l installation ait t totalement rem...

Page 39: ...entretiens des parties lectriques install es par ex ventilateurs sondes de temp rature etc et des dispositifs branch s au thermo produit l o il existe une installation hydraulique 8 1 FONCTIONNEMENT N...

Page 40: ...ait donc n cessaire de les remplacer En cas d humidit du local o est situ l appareil placer des sels absorbants l int rieur du foyer de celui ci Prot ger les pi ces int rieures en fonte avec de la vas...

Page 41: ...cipient doit tre plac sur un sol ignifuge loin de mat riaux inflammables jusqu l extinction et refroidissement complet Contr ler en le nettoyant au moins une fois par an la prise d air externe 10 4 EN...

Page 42: ...ca S p a will be sanctioned from the laws IT LEGENDA EN KEY C Circolatore C Circulator CM Collettore Mandata CM Supply collector CR Collettore Ritorno CR Return collector F Flussostato F Flow switch M...

Page 43: ...Pumpe C Circulateur CM Kollektor Zulauf CM Collecteur refoulement CR Kollektor Rucklauf CR Collecteur d foulement F Flussmesser F Fluxostat M Manometer M Manom tre P Pumpe P Circulateur P1 Pumpe Nr 1...

Page 44: ...IA DA BOILER M Tubo di carico Load pipe Zufuhrrohr OFF ON 1 2 3 4 5 6 T 1 2 3 4 5 6 7 20 7 C V VECTS V V 6 bar VSP Bollitore CM CR VMTA S 9196632 16 02 2009 VDM VB VST T M V VEAC VSP 1 5 bar TERMOPROD...

Page 45: ...1 2 3 4 5 6 T 1 2 3 8 5 6 7 9 20 7 C T Boiler VSP 95 C M VMTA 9196627B 19 11 2009 VST TS 3 bar VR V VEC VR VEC VR VR VEC VSP 6 bar VB VMS CM CR V V TERMOPRODOTTO IMPIANTO a vaso chiuso per TERMOPRODOT...

Page 46: ...SA LA NORDICA CON ABBINATA PRODUZIONE DI ACQUA SANITARIA DA ACCUMULO SANITARIO M OFF ON 1 2 3 4 5 6 T 3 3 5 6 7 7 12 11 10 20 21 A B C D 1 TERMOPRODOTTO 55 3 2 1 M R CB A B 20 IT EN A ON OFF ON OFF B...

Page 47: ...N E chaudi re 2 RITORNO caldaia RETURN central heating RUCKLAUF Kessel RETOUR chaudi re 3 Sonda regolatore Regulator probe Einstellsonde Sonde r gulateur A ENTRATA Sistema integrato DSA INLET Integrat...

Page 48: ...ento Yield Wirkungsgrad Rendement 82 7 Allacciamento caldaia Boiler hook up Durchmesser Zufuhr und R ckf hrungsverbindungen in Zoll Raccordement chaudi re 1 F Depressione al camino mmH2 O Depression a...

Page 49: ...Au enlufteinlass cm Prise air externe cm 20 Temperatura ottimale di esercizio C Optimal operating temperature C Optimale Betriebstemperatur in C Temp rature optimale d exercice C 70 75 Piedini regolab...

Page 50: ...FLY IDRO DSA 50 7193505 IT EN DE FR 1 2 3 14 MONTAGGIO ASSEMBLY MONTAGE 14 1 MAIOLICHE EXTERNAL FACES VERKLEIDUNG CADRE FRAGILE ZERBRECHLICH FRAGILE ZERBRECHLICH FRAGILE ZERBRECHLICH...

Page 51: ...FLY IDRO DSA 7193505 IT EN DE FR 51 SILICONE SILICONE 4 5 5 FRAGILE ZERBRECHLICH FLY Idro DSA Infinity FLY Idro DSA Crystal...

Page 52: ...sgrad 40 viter conduits de chemin e avec section rectangulaire interne dont le rapport soit diff rent du dessin Efficience 40 m diocre 1 Comignolo industriale ad elementi prefabbricati consente un ott...

Page 53: ...ch depuis le toit 45 1 30 m 0 50 m oltre il colmo above the roof ridge vom First outre la ligne de fa te 1 30 m 2 00 m dal tetto from the roof vom Dach depuis le toit 60 1 20 m 0 50 m oltre il colmo a...

Page 54: ...Picture 5 Figura 5 Abbildung 5 Figure 5 Picture 6 Figura 6 Abbildung 6 Figure 6 FLY IDRO DSA 54 7193505 IT EN DE FR 4 5 1A 2A A B 50 cm 100 cm...

Page 55: ...Figura 8 Picture 8 Abbildung 8 Figure 8 Figura 7 Picture 7 Abbildung 7 Figure 7 FLY IDRO DSA 7193505 IT EN DE FR 55 7 A 6...

Page 56: ...6 7193505 IT EN DE FR 8 9 D A B C A Chiusura ermetica Hermetic closure Hermetischer Verschluss Fermeture hermetique B Acciaio Inox Stainless steel Stainless steel Acier Inox C Tamponamento Plugging Ab...

Page 57: ...13240 Informazioni marcatura CE CE Marking information Auszeichnungsinformationen Informations marquage CE Vedi allegato See enclosure Siehe Beilage Voir annexe Condizioni particolari Particular cond...

Page 58: ...ammessa Maximum operating pressure Maximale Betriebsdruck Pression hydrique de service maximum autoris e 3 bar Temperatura gas di scarico Flue gas temperature Abgastemperatur Temp rature gaz d chappem...

Page 59: ......

Page 60: ...bindend Die Firma beh lt sich vor ohne Vorank ndigung nderungen und Verbesserungen vorzunehmen La Maison constructrice n est pas tenue respecter ces donn es et ces mod les elle se r serve le droit d...

Reviews: