MODEL TPS - INSTRUCTIONS AND TROUBLESHOOTING INFORMATION
7 OF 20
CPN 40615
2.5
FILTERING
Single phase units are 30Mv. RMS and three phase units are 100Mv. RMS when connected to a battery
with an ampere-hour capacity of four times the output current capacity of the charger (32 DBRN “C”
message weighting on unit’s 48 volts or less).
2.6
MEAN TIME BETWEEN FAILURE
The mean time between failure (MTBF) in excess of 175,000 hours at 50 degrees C.
3.0
INPUT RATINGS
3.1
A.C. VOLTAGE
Taps are provided for nominal single phase a.c. input voltages of 120/208/240 Vac, with an a.c. input
voltage range of +/-10% of nominal.
The 75 and 100 amp units are rated for three phase inputs and available in 208/ 240 or 480 Vac inputs.
3.2
INPUT FREQUENCY RANGE
57 to 63 Hz. (60 HZ nominal)
47 to 57 HZ. (50 HZ nominal)
3.3
INPUT CURRENT
(Refer to TABLE 1)
4.0
TYPICAL ELECTRICAL SPECIFICATIONS
(Refer to TABLE 1)
5.0
STANDARD FEATURES
5.1
INPUT PROTECTION:
AC BREAKER
Single Phase Units -
A two-pole circuit breaker opens both sides of the
a.c. service for 120-208 or 240 on single phase
models, 50 amps or less.
Three Phase Units -
A three-pole circuit breaker opens all three legs of
the a.c. service.
5.2
OUTPUT PROTECTION:
A two pole d.c. breaker is provided on all 50 amp or less units.
Current limiting is adjustable from 90% to 120% of rated load, limits the d.c. output current. Factory
set at 115% of rated output.