background image

INSTRUCTION MANUAL FOR PC63 CAGE 

Page 3 of 10 

 

PREPARING TO CHARGE 

 

If necessary to remove the battery connections, always remove grounded terminal from the battery first.  Make sure 

all loads are disconnected and unit is off, so as not to cause an arc. 

 

Be sure the area around the battery is well ventilated while the battery is being charged. 

 

When cleaning battery terminals, be careful to keep corrosion from coming in contact with eyes. 

 

Study all the battery manufacturer’s specific precautions such as removing or not removing cell caps while charging, 

recommended rates of charge, and maintenance procedures. 

 

UNIT LOCATION 

 

Never place this unit directly above the battery.  Gases from the battery will corrode and damage equipment.  A sealed 

maintenance free or valve regulated lead acid (VRLA) may be placed below this equipment. 

 

Never allow the battery electrolyte to drip on this unit when reading the specific gravity or filling the battery. 

 

Do not operate this unit in a closed-in area or restrict ventilation in any way. 

 

Do not set a battery on top of this unit. 

 
 

D.C. CONNECTION PRECAUTIONS 

Connect and disconnect D.C.  output cables only after setting all of this unit's switches to off position. 

 
 

GROUNDING INSTRUCTIONS 

This  battery  charger  should  be  connected  to  a  grounded,  metal,  permanent  wiring  system;  or  an  equipment  grounding 
conductor  should  be  run  with  circuit  conductors  and  connected  to  equipment-grounding  terminal  or  lead  on  battery 
charger.  Connections to battery should comply with all local codes and ordinances. 

 

CAUTION: DO NOT PULL ON OUTPUT CABLES WHEN DISCONNECTION CHARGER FROM BATTERY 

Summary of Contents for PC63 Series

Page 1: ...OR PC63 CAGE Page 1 of 10 INSTRUCTION MANUAL FOR PC63 CAGE ECN DATE CPN106833 16816 6 05 106 BRADROCK DRIVE DES PLAINES IL 60018 847 299 1188 FAX 847 299 3061 ISSUE DATE 15689 12 02 INSTRUCTION DRAWIN...

Page 2: ...THE INSTRUCTIONS EXACTLY To reduce risk of battery explosion follow these instructions and those published by the battery manufacturer and manufacturer of any equipment you intend to use in the vicin...

Page 3: ...orrode and damage equipment A sealed maintenance free or valve regulated lead acid VRLA may be placed below this equipment Never allow the battery electrolyte to drip on this unit when reading the spe...

Page 4: ...to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for handling Unti...

Page 5: ...4V A63 24V A63 PC63 30 48V 130V 48V A63 48V A63 TPCD DISTRIBUTION CENTER PC63 60 24V 130V 24V A63 24V A63 TPCD DISTRIBUTION CENTER PC63 120 12V 130V 12V A63 12V A63 12V A63 12V A63 Input DC The A63 mo...

Page 6: ...ept a TPCD connect the negative wire from the battery must be connected to the terminal marked negative and the positive wire from the battery must be connected to the terminal marked positive on the...

Page 7: ...ENT CUSTOMER CONNECTION EQUIPMENT GROUNDING CONDUCTOR MINIMUM FUSE SIZE WIRE SIZE REQUIREMENT CUSTOMER CONNECTION EQUIPMENT GROUNDING CONDUCTOR MINIMUM 1 14 14 150 1 6 3 14 14 175 1 0 6 4 14 14 200 2...

Page 8: ...enotes all sizes larger than 0000 are expressed in MCM TABLE OF CONVENTIONS CMA Cross section of wire in circular MIL area A Ultimate drain in amperes LF Conductor loop feet MAX AMP Maximum allowable...

Page 9: ...ers and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REPEAT ALL WITH THE ADDITION OF 1 Filter...

Page 10: ...lity for proper installation installation adjustments and service arrangements Should minor adjustments be required the local La Marche Sales Representative should be contacted to provide this service...

Reviews: