7
3.1.1
Controls
Button
Function
Mute / Operation Mode Menu
1 Second Press: Mute the buzzer
Long Press: Enter Operation Mode menu
Up / Charge Voltage Menu
1 Second Press: Raise current setting/value
5 second Press: Enter Charge Voltage menu
Down / Charge Current Menu
1 Second Press: Lower current setting/value
5 second Press: Enter Charge Current menu
ON/OFF
ON/OFF control
3.1.2
LCD Display Indicators
LCD Parameter Icon
LCD Display
Description
AC Mains Input Voltage Meter
AC Output Frequency Meter
AC Output Voltage Meter
Equipment Operating Mode Selection*
Grid Priority
Mode
Energy-Saving
Mode
Battery Priority
Mode
*Operating Mode can be entered by long pressing the Function button for seconds.
Battery Icon
LCD
Display
Battery Voltage Values
12VDC
24VDC
48VDC
96VDC
•
Below 10.5V
1
•
10.5V
–
11.2V
•
Below 21V
1
•
21V
–
22.4V
•
Below 42V
1
•
42V
–
44.8V
•
Below 84V
1
•
84V
–
89.6V
11.2V
–
11.6V
22.4V
–
23.2V
44.8V
–
45.2V
89.6V
–
90.4V
11.6V
–
12.1V
23.2V
–
24.2V
45.2V
–
48.4V
90.4V
–
96.8V
12.1V
–
12.5V
24.2V
–
25V
48.4V
–
50V
96.8V
–
100V
Above 12.5V
Above 25V
Above 50V
Above 100V
1
Blinking
Load Usage Icon
LCD Display
Function
Output overload alarm; inverter has surpassed 100% capacity
0%
to
25% 25%
to
50% 50%
to
75% 75%
to
100%