background image

A48 INSTRUCTION MANUAL / ADJUSTMENTS / WARRANTY 

Page 2 of 8 

 
This  manual  contains  important  safety  and  operating  instructions  for  the  La  Marche  Power  Conversion 
Equipment. 
 
Before using this equipment, read all instructions and cautionary markings on  (1) unit, (2) battery, and 
(3) product using the battery. 
 

CAUTION:  To reduce risk of injury and/or damage to the batteries, use only 
the type of batteries specified on the charger.

 

 

Do not

 expose equipment to rain or snow. 

Do not 

operate equipment if it has received a sharp blow, been dropped, or otherwise damaged in any 

way; take it to a qualified serviceman. 

Do  not

  disassemble  this  unit;  take  it  to  a  qualified  serviceman  when  service  or  repair  is  required.   

Incorrect re-assembly may result in a risk of electric shock or fire. 
 
To reduce risk of electric shock, disconnect this unit from the AC   supply, or batteries and  loads  before  
attempting  any maintenance or cleaning.  Turning off controls will not reduce this risk. 
 
WARNING – THERE IS A RISK OF EXPLOSIVE GASSES AND WORKING IN THE VICINITY OF A BATTERY 
IS  DANGEROUS.    SOME  BATTERIES  GENERATE  EXPLOSIVE  GASES  DURING  NORMAL  BATTERY 
OPERATION.    FOR  THIS  REASON,  IT  IS  OF  UTMOST  IMPORTANCE  THAT  EACH  TIME  BEFORE  USING 
THIS UNIT, YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY. 

 
To  reduce  risk  of  battery  explosion,  follow  these  instructions  and  those  published  by  the  battery 
manufacturer and manufacturer of any equipment you intend to use in the vicinity of the battery.  
 
Review cautionary marking on all products . 
 

PERSONAL PRECAUTIONS:

 

1.

 

Someone  should  be  within  range  of  your  voice  or  close  enough  to  come  to  your  aid  when  you 

work near a battery. 

2.

 

Have  plenty  of  fresh  water  and  soap  nearby  in  case  the  battery  electrolyte  contacts  skin, 

clothing, or eyes. 

3.

 

Wear complete eye protection and clothing protection. Avoid touching eyes while working near a 

battery. 

4.

 

If the battery electrolyte contacts skin or clothing, wash immediately with soap and water.  If the 

electrolyte enters the eye, immediately flood the eye with running cold water for at least ten (10) 
minutes and get medical attention immediately. 

5.

 

Never smoke or allow a spark or flame in vicinity of a battery. 

6.

 

Be extra cautious, DO NOT drop metal onto a battery.  It might spark or short-circuit the battery 

or cause an explosion. 

7.

 

Remove  personal  metal  items  such  as  rings,  bracelets,  necklaces,  and  watches  when  working 

with a battery.    A battery can produce a short-circuit current high enough to weld these items 
causing severe burns. 

8.

 

NEVER charge a frozen battery. 

IMPORTANT 

SAFETY INSTRUCTIONS 

FOR THE 

LA MARCHE POWER CONVERSION EQUIPMENT 

SAVE THESE INSTRUCTIONS

 

Summary of Contents for A48

Page 1: ...ge 1 of 8 A48 A48B base plate BATTERY CHARGER ECN DATE CPN41054 16816 6 05 15349 07 07 02 16041 6 03 14575 2 01 106 BRADROCK DRIVE DES PLAINES IL 60018 1967 847 299 1188 FAX 847 299 3061 ISSUE DATE 12...

Page 2: ...OU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY To reduce risk of battery explosion follow these instructions and those published by the battery manufacturer and manufacturer of any equipment...

Page 3: ...y will corrode and damage equipment A sealed maintenance free or valve regulated lead acid VRLA may be placed below this equipment Never allow the battery electrolyte to drip on this unit when reading...

Page 4: ...claim to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for handling...

Page 5: ...r example a negative grounded engine must have a charger with two positive isolated terminals and one common negative terminal A voltage sensing relay is provided to automatically transfer the output...

Page 6: ...attery to accomplish this setting 7 The unit should be oscillating from float to high at 2 33 volts per cell If the unit does not transfer back to high rate adjust the set D pot counterclockwise until...

Page 7: ...l meters and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REPEAT ALL WITH THE ADDITION OF 1 Fi...

Page 8: ...r 2 If the purchaser elects not to return the equipment to the factory and wishes a factory service representative to make adjustments and or repairs at the equipment location La Marche s field servic...