background image

MODEL A45E INSTRUCTION MANUAL

Page 6 of 12

INSTALLATION INFORMATION

Figure 1 lists the a.c. input and the d.c.  output minimum  wire   size requirements.  At distances

exceeding 10 feet, the  d.c. wire size should be chosen to keep the voltage difference between  the

units  d.c.  output terminals and the battery at   less   than ½ volt when the unit is fully loaded.

ELECTRICAL CONNECTIONS & FIELD WIRING

An a.c. input fuse block is provided for connecting the a.c. input.  A ground wire must be connected to

the units’ case ground.

A.C. INPUT

A fuse block is provided within the unit for a.c. input connections.  Before connecting the a.c. input cable,

check the line power with the internal a.c. voltage connections, if necessary change the a.c. jumper
connections to match the a.c. input.  Refer to schematic drawing included in manual or tap jumper card

inside door panel.

D.C. OUTPUT

NOTE:  MOST UNITS HAVE D.C. OUTPUT CABLES WHEN ORDERED.

Make sure that the battery which is being connected to the battery charger matches the cell type and

number of cells that is marked on the charger nameplate.

***OBSERVE PROPER POLARITY!***

The negative wire from the battery must be connected to a terminal marked “NEGATIVE” or “NEG” and

the positive wire from the battery must be connected to the terminal marked “POSITIVE” or “POS” on the

battery charger.

OPERATION

START UP (Electronic Timer)

After the installation has been completed, the unit is ready for operation.  Be sure that the battery

charger is the correct type for the battery that is to be charged.

CAREFULLY READ AND ADHERE TO ALL BATTERY AND BATTERY CHARGER INSTRUCTIONS

AND SAFETY WARNINGS.

A. With the a.c. input connected to the charger, turn the on/off switch to the “on” position.

B.  Connect the battery to the charger.  After a 5 second delay, which assures proper battery connection,

the input contactor will close.  The battery charger will start to charge and the “ON CHARGE” light will
turn on. This completes the “Autostart” sequence.

The display will read, OUTPUT AMPS, push the select switch down once and the display will read D.C.

VOLTAGE, a second push the display will read AMP/HOURS RETURNED and a third push the display will

read ELAPSED TIME.  Push the select switch UP and the unit will equalize the battery.

C. When the “80% CHARGE” point is reached in the charge cycle, the “80%” light will turn on and a three

(3) hour timer will start.  (If in the equalize mode, the unit will operate for six (6) hours after 80% light

turns on.)

Summary of Contents for A45E

Page 1: ...Page 1 of 12 MODEL A45E BATTERY CHARGER ECN DATE CPN35921 14575 2 01 15349 10 8 02 14268 10 00 106 BRADROCK DRIVE DES PLAINES IL 60018 1967 847 299 1188 FAX 847 299 3061 ISSUE DATE 10378 9 96 INSTRUCT...

Page 2: ...UCTIONS EXACTLY To reduce risk of battery explosion follow these instructions and those published by the battery manufacturer and manufacturer of any equipment you intend to use in the vicinity of the...

Page 3: ...amage equipment A sealed maintenance free or valve regulated lead acid VRLA may be placed below this equipment Never allow the battery electrolyte to drip on this unit when reading the specific gravit...

Page 4: ...to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for handling Until...

Page 5: ...The Model A45E features Microprocessor based control Automatic start stop circuitry Automatic Sensing of Fully Charged Battery Automatic 12 hour override timer 3 Hour timing after 80 normal mode 6 Hou...

Page 6: ...m the battery must be connected to a terminal marked NEGATIVE or NEG and the positive wire from the battery must be connected to the terminal marked POSITIVE or POS on the battery charger OPERATION ST...

Page 7: ...n the a c has returned to normal the charge cycle resumes where it left off CAUTION Turn the on off switch to the off position when disconnecting the battery during the charge cycle to prevent arcing...

Page 8: ...MODEL A45E INSTRUCTION MANUAL Page 8 of 12 FIGURE 1...

Page 9: ...charging problems that arise from a varying line when charging continually day and night or for two or three shift operations The unit is self protecting when subjected to abnormal overloading condit...

Page 10: ...ents must be made the taper and shutdown point may be adjusted This adjustment may be made by moving the red slider band on the voltage reference variable resistor RV1 Moving this slider band toward t...

Page 11: ...1 Check battery for defective or shorted cells 2 S2A 122A p c board may be defective CODE 0005 Not used Problem Failure light CODE 0006 1 Check for defective or shorted cells in battery 2 Check finis...

Page 12: ...f the purchaser elects not to return the equipment to the factory and wishes a factory service representative to make adjustments and or repairs at the equipment location La Marche s field service lab...