L.J. Wing GA-320 Installation, Operation And Maintenance Manual Download Page 3

fan unit removal:

Model #

Allow (in.)

GA-320

42"

GA-400

48"

GA-640

50"

GA-800

54"

GA-960

60"

GA-1280

60"

4. Approximately 12" at furnace ends for

proper air inlet.

D. Unit should not be installed unless an ade-

quate flue can be provided.

IV. FLUE CONNECTIONS

The flue collector is of one-piece sheet metal

design with integral draft diverter. Flue outlets are
factory arranged to face upward.

Flue Dimensions

Model #

Dia. (in.)

GA-320

5"

GA-400

5"

GA-640

6"

GA-800

5"

GA-960

5"

GA-1280

6"

A. Consult local codes and regulations.

B. Refer to attached furnace manual for specific

venting instructions.

V. GAS PIPING

A. Connect gas piping in accordance with local

codes and authorities having jurisdiction.

B. Refer to attached furnace manual for specific

gas piping instructions.

VI. WIRING DETAILS

A. All units have been completely pre-wired and

tested at the factory and are ready for con-
nection to the external power source and to
the operating controls. See specific wiring
drawing accompanying installation instruc-
tions shipped with unit.

B. Make all external wiring in accordance with

the National Electric Code and local ordi-
nances.

VII. START UP INSTRUCTIONS

A. Energize electrical system through optional

main disconnect switch.

B. Refer to attached furnace manual for start up

instructions on pilot and main gas burners.

VIII. PRE-START INSPECTION

This inspection is extremely important and

should be completed with the greatest care given
to detail. A good pre-start inspection will insure
against possible unit damage on start-up and will
save valuable analysis time in the event a malfunc-
tion should occur on start-up.

• Check to see that all factory installed pipe

plugs have been removed.

• Check supply voltage against unit voltage.

• Check all electrical connections for tightness

at all terminals in the main control panel and
optional remote control panel.

• Check that all fuses are installed.

• Check fan area to insure freedom of rotation.

• Check all areas for cleanliness.

• Secure all access doors.

• If revolving discharge section is ordered, the

gear motor is secured so that it will not
become damaged during transit. Check to
see that gear motor has been loosened and
works freely against the spring.

3