Gas Pipe Construction
Gas pipe construction must be done by gas dealer or gas pipe installation dealer.
1
The diameter of the gas pipes for this
unit is 15A(PT 1/2″
) or 20A(PT 3/4″
)
for each model.
See specifications in this manual.
2
Gas pipes must be metal pipes that
were approved by metal pipe or gas
part inspection testing. When using
LP gas, do not install the fuse cork
and a middle gas shut-off valve
must be installed(installing fuse cork
can cause malfunctions).
3
When using LP gas, use caution of
the following items :
y
LP gas governor should be house
hold low pressure governor that is
proper for gas usage indicated.
y
LP gas container should be 50kg
and use two or more containers
(connect a twin valve to supply
gas from the two containers
simultaneously).
※ In case the container capacity is
small, evaporation capacity is
small that it may cause gas
waste and normal operation may
be hindered.
4
Boiler gas pipe must be directly
connected to the main pipe and do
not connect it along with other gas
appliances.
CAUTION
In every case for gas pipe construc-
tion, please, follows National and
Local laws and roles.
5