9.Optional Accessories

Multi-Tran MODEL 8008 extends the
capability of KEW SNAP 2002PA or KEW
SNAP 2002R, allowing measurement up
to 3000A or on a large bus-bar or
conductor.

Set the function selector switch to "

400A"

As shown in the figure below, clamp
KEW SNAP 2002PA or KEW SNAP
2002R onto the pickup coil of MODEL
8008.

Clamp MODEL 8008 onto the bus-bar
or conductor under test.

Take the reading on KEW SNAP
2002PA or KEW SNAP 2002R and
multiply it by 10.

MAX
150㎜

MAX
100㎜

10.Disposing the Product

Waste Electrical and Electronic Equipment (WEEE), Directive 2002/96/EC

This Product complies with the WEEE Directive (2002/96/EC) marking
requirement.
The affixed product label (see below) indicates that you
must not discard this electrical/electronic product in
domestic household waste.

Product Category

With reference to the equipment types in the WEEE
directive Annex 1, this product is classified as a

Monitoring and Control instrumentation

product.

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for KEW SNAP 2002PA

Page 1: ...NSTRUCTION MANUAL KEW SNAP SERIES KEW SNAP 2002P A 2002R DIGITAL CLAMP METER KYORITSU ELECTRICAL INSTRUMENTS WORKS LTD www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Page 2: ...itch Setting and Operation 11 6 Measurement 6 1 Current Measurement 12 6 2 Voltage Measurement 14 6 3 Resistance Measurement 15 7 Notes on Functions 7 1 Data Hold 17 7 2 Sleep Function 17 7 3 Output for Recorder 18 7 4 Mode Switching Function 19 8 Battery Replacement 20 9 Optional Accessories 21 10 Disposing the Product 21 www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSu...

Page 3: ... to follow measurement procedures described in the manual Be sure to understand and follow all safety instructions contained in the manual Be sure to observe the above instructions Failure to follow the above instructions may cause injury instrument damage and or damage to equipment under test The symbol indicated on the instrument means that the user must refer to related parts in the manual for ...

Page 4: ... and instrument damage or serious personal injury may be caused WARNING Never attempt to make any measurement if any abnormal conditions are noted such as broken case cracked test leads and exposed metal parts Do not turn the function selector switch with test leads connected to the instrument Do not install substitute parts or make any modification to the instrument Return the instrument to your ...

Page 5: ...ents categorized as CAT I to CAT IV and called measurement categories Higher numbered categories correspond to electrical environments with greater momentary energy so a measuring instrument designed for CAT III environments can endure greater momentary energy than one designed for CATII CAT I Secondary electrical circuits connected to an AC electrical outlet through a transformer or similar devic...

Page 6: ...ndards IEC61010 1 CAT Ⅲ 600V CAT Ⅱ 1000V Pollution degree 2 IEC61010 031 IEC61010 2 032 Data hold function to allow easy readings in dimly lit or hard to read locations Sleep feature to conserve battery power Permits easy continuity check with a beeper Provides a dynamic range of 4 000 counts full scale Provides wide measuring range of voltage and resistance in auto ranging Wide frequency range fr...

Page 7: ...y Frequency Range 1 5 rdg 0 5mV 50 60Hz 2 5 rdg 0 5mV 40 1kHz 1 5 rdg 0 5mV 50 60Hz 3 5 rdg 0 5mV 40 1kHz 3 5 rdg 50 60Hz Maximum Measurement Time Continuous 15min 5min Range 40V 400V 750V Range 40V 400V 1000V Range 400Ω 4kΩ 40kΩ 400kΩ Range 400A 2000A AC Voltage V Auto ranging Initially set to the 40V range Input impedance is about 1MΩ DC Voltage V Auto ranging Initially set to the 40V range Inpu...

Page 8: ...ut condensation Conductor Size Approx 54 5 diameter max Overload Protection 2400A AC for 10sec 1200V AC DC for 10sec 600V AC for 10sec Withstand Voltage 5320V AC for 5 seconds between electrical circuit and housing cases or metal parts of jaws Insulation Resistance 10MΩ or greater at 1000V between electrical circuit and housing cases or metal parts of jaws Safety Standard IEC 61010 1 Measurement C...

Page 9: ...mV 40 1kHz 2 5 rdg 0 5mV 45 65Hz 3 5 rdg 0 5mV 40 1kHz 4 5 rdg 50 60Hz Maximum Measurement Time Continuous 15min 5min Range 40V 400V 750V Range 40V 400V 1000V Range 400Ω 4kΩ 40kΩ 400kΩ Range 400A 2000A AC Voltage V Auto ranging 9 counts or less is corrected to 0 Initially set to the 40V range Input impedance is about 1MΩ When approx 300V or more is applied to the instrument instantaneously the mea...

Page 10: ...y without condensation Conductor Size Approx 54 5 diameter max Overload Protection 2400A AC for 10sec 1200V AC DC for 10sec 600V AC for 10sec Withstand Voltage 5320V AC for 5 seconds between electrical circuit and housing cases or metal parts of jaws Insulation Resistance 50MΩ or greater at 1000V between electrical circuit and housing cases or metal parts of jaws Safety Standard IEC 61010 1 Measur...

Page 11: ... 9 www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Page 12: ...nal COM Terminal OUTPUT Terminal Test Leads Mー7107 Recorder Output Plug Mー8102 Data Hold Mode Resistance Voltage Current Peak Mode Measurement Battery Voltage Alert Continuity Check Mode Negative Potential AC Current DC Current LCD INDICATOR Function Switch Barrier www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Page 13: ...unction which automatically powers the instrument down in a certain period of time after the last switch operation To operate the instrument in this case set the switch back to the OFF position then to the desired position or press any button 5 2 Checking Switch Setting and Operation Make sure that the function selector switch is set to the correct position the instrument is set to the correct mod...

Page 14: ...measuring current is not less than 1000A make sure to stop measurement within the maximum measuring time shown below Otherwise transformer jaws may heat to cause a fire or deformation of molded parts which will degrade insulation 1000 1500A 15min 1500 2000A 5min Keep your fingers and hands behind the barrier during measurement 6 1 1 AC Current Measurement Normal Mode Set the function selector swit...

Page 15: ... the trigger to open the transformer jaws and clamp them onto the conductor under test Then press the reset switch The display shows the current s crest value divided by the square root of two Therefore when the current is sinusoidal the reading equals RMS value To reset the display press the reset switch Note When this is done the reading goes off for about one second After the measurement is ove...

Page 16: ...st lead into the COM terminal Connect the other end of the test leads to the circuit under test Take the reading on the display When the red lead is the negative potential the ー sign is shown on the display 6 2 2 AC Voltage Measurement Set the function selector switch to the V position Slide the terminal cover to the left Plug the red test lead into the V Ω terminal and the black test lead into th...

Page 17: ...tor switch to the Ω position Slide the terminal cover to the left Plug the red test lead into the V Ω terminal and the black test lead into the COM terminal Short the tip of the test leads and check whether the display reads 0 Connect the tip of the test leads to the circuit under test Take the reading on the display NOTE When shorting the tip of the test leads the display may read a very small re...

Page 18: ...isplay Short the tip of the test leads and make sure that the display reads 0 and the buzzer beeps Connect the tip of the test leads to the circuit under test The display reads the resistance and the buzzer beeps when the reading is not more than about 50Ω NOTE When shorting the tip of the test leads the display may read a very small resistance instead of 0 This is the resistance of the test leads...

Page 19: ...AC current range When the sleep function is activated the data hold mode turns to the normal mode 7 2 Sleep Function This is a function to prevent the instrument from being left powered on in order to conserve battery life The instrument automatically enters the sleep powered down mode about 10 minutes after the last switch operation To exit the sleep mode press the data hold reset or mode switch ...

Page 20: ... selector switch to the 400A or 2000A position Slide the terminal cover to the right and insert the recorder output plug into the OUTPUT terminal for connection with a recorder or other recording device NOTE Output voltage is 1mV A on the 400A range and 0 1mV A on the 2000A range Set an appropriate input sensitivity on the recorder The peak hold function does not apply to the recorder output even ...

Page 21: ... normal mode and can be switched to the peak or continuity check mode by means of the mode switch See section 6 1 2 for peak current measurement and section 6 3 2 for continuity check Normal Peak Peak current value is displayed Response time 10ms PEAK is shown on the display Press the mode switch Normal Continuity Check The buzzer beeps if the resistance is not more than about 50Ω The buzzer symbo...

Page 22: ...E If the instrument is powered on but the display blanks or BATT is shown on the display replace the batteries Set the function selector switch to the OFF position Unscrew and remove the battery compartment cover on the bottom of the instrument Replace the batteries observing correct polarity Use two new R6P batteries Replace and screw the battery compartment cover 8 Battery Replacement Screw Batt...

Page 23: ...02PA or KEW SNAP 2002R and multiply it by 10 MAX 150 MAX 100 10 Disposing the Product Waste Electrical and Electronic Equipment WEEE Directive 2002 96 EC This Product complies with the WEEE Directive 2002 96 EC marking requirement The affixed product label see below indicates that you must not discard this electrical electronic product in domestic household waste Product Category With reference to...

Page 24: ...E 11 11 Kyoritsu reserves the rights to change specifications or designs described in this manual without notice and without obligations www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Reviews: