background image

When choosing a site, avoid trees, buildings or obstructions, 
which could cast shadows on PV modules especially during 
the winter season when the arc of the sun is lowest over the 
horizon. 

 

5. MODULE TILT ANGLE 

The  PV  modules  produce  more  power  when  they  are 
pointed directly at the sun. 
For grid-tie installations where the PV modules are attached 
to a permanent structure, PV modules should be tilted at an 
angle equal to the site's latitude. This will typically result in 
the highest annual energy output.

 

 

6. INSTALLING PV MODULES

 

A minimum spacing of 2

” (50 mm) is required between the 

PV module and the mounting surface around the perimeter 
of  PV  array.  The  PV  modules  may  be  installed  in  various 
applications  utilizing  a  variety  of  support  structure  options 
and  attachment  methods.

 

For  optimal  performance  in  all 

applications, clearance between the module frame and the 
mounting surface is required to allow cooler ambient air to 
circulate  around  the  back  of  the  module

 

and  to  avoid 

module and/or wiring damage. A minimum of .13

” (3.2 mm) 

spacing must also  be maintained  between module frames 
to allow for thermal expansion.  
 
The PV modules may be attached to a support structure by 
the  following  methods.  The  structure  should  have  enough 
strength  to  achieve  the  mounting  span.  When  installing 
modules in a snowy area, an appropriate countermeasure 
has  to  be  taken  to  prevent  possible  damage  to  the  lower 
side frame by slipping snow (e.g. attach supporting parts to 
the lowest modules.). Any damage caused by snow or such 
countermeasures is not covered under warranty. 
 

BOLTING

: Use 5/16

”(8mm) stainless steel

 

(or equivalent in 

corrosion resistance) hardware through the existing .35

” (9 

mm) diameter mounting holes in the module frame and then 
through  the  holes  on  the  support  structure.  Tighten  the 
screws  with  adequate  torque  (usually  132  in-lb;  refer 
structure manufacturer specifications). Refer to the module 
drawings (Section 12) for the position of mounting holes. 
 

CLAMPING

: Fasten modules firmly using clamps which will 

not be deformed by wind load or snow load. Clamps should 
be attached to support structure with 1/4

” (6mm) or larger 

bolt and nut using torque values specified by structure 
manufacturer. Bolt and nut should be stainless steel or 
equivalent in corrosion resistance. Support structure should 
be set perpendicular to the long side of frame, and should 
support the bottom of module at least 0.39

” (10mm) width. 

Clamps must not bend the module frame nor damage the 
surface of the frame. Clamps also must not shade the 
sunlight incidence on glass surface. Take measures to 
prevent module from falling off clamps. Refer to the 
‘CLAMPING AREA’ in the module drawings (Section 12) for 
the permissible clamping range. 
 
The clamp specification is below; 

A- SUS304 or equivalent

t: thickness

L: width

a: overlap

0.079" (2.0mm)

 and over

min. 2.76"

      (70mm)

0.098" (2.5mm)

 and over

min. 1.73"

     (44mm)

0.12" (3.0mm)

and over

min. 1.50"

     (38mm)

B-anodized aluminum AL6063-T5 or equivalent

t: thickness

L: width

a: overlap

0.12" (3.0mm)

 and over

min. 2.28"

      (58mm)

0.14" (3.5mm)

 and over

min. 1.65"

     (42mm)

0.16" (4.0mm)

and over

min. 1.50"

      (38mm)

min. 0.28"

    (7mm)

min. 0.20"
     (5mm)

 

a

t

L

 

 
The clamp shape and dimensions above are for reference 
only,  and  any  damage  caused  by  clamps  is  not  covered 
under warranty. 
 

7. MODULE WIRING 

The PV module comes pre-wired. Each module has two #12 
AWG  type  PV-wire  stranded  sunlight  resistant  output 
cables 

each 

terminated 

with 

R51-7/P51-7 

(MC4 

compatible). The positive (+) terminal has a male connector 
while the negative (-) terminal has a female connector. The 
module wiring is solely for series connections only, i.e. male 
(+)  to  female  (-)  interconnections.  Series  and/or  parallel 
connections shall be made with #10-14 AWG type PV-wire 
stranded  output  cables,  having  sunlight  resistant  and 
temperature rating of 90

 minimum, with R51-7/P51-7 (or 

MC4: PV-KST4/KBT4).  
 

NOTE

:  When  making  connections  with  the  connectors, 

make  sure  the  array  is  disabled. 

DO  NOT  MAKE 

CONNECTIONS  WHILE  UNDER  LOAD

.

  Module  output 

connections are marked “Do not disconnect under load”. 

NOTE

 MAXIMUM SYSTEM VOLTAGE IS 600 VDC. 

The PV module and most PV system components have  a 
maximum  system  voltage  rating  of  600  volts  DC.  Some 
grid-tie systems operate at or near this voltage rating. Like 
other polycrystalline PV modules, the open circuit voltage of 
the  PV  modules  increases  as  the  ambient  temperature 
decreases.  Maximum  system  voltage  is  computed  as  the 
sum of the open-circuit voltage of the series-connected PV 
modules  for  the  lowest  expected  ambient  temperature. 
Refer  to  the  National  Electrical  Code  Article  690-7(A)  for 
determining the maximum number of the PV modules that 
can be placed

 

in series. Temperature coefficients, specific 

to  the  module  of  use,  can  be  used  to  provide  the  most 
accurate  prediction  of  module  voltage  under  temperature 
extremes. 
NOTE: Limit the maximum number of series connections of 
the PV modules so that the system voltage is 600 V or less. 
NOTE:  Do  not  connect  the  modules  in  parallel  without 
maximum over current protection. 
NOTE: The minimum radius that the cable can be bent for 
the PV modules is 1.14

” (29mm). 

NOTE: Under normal conditions, PV modules may produce 
more current and/or  voltage than reported  in the standard 
test  conditions.  Therefore,  when  voltage  evaluations  for 
components, capacity of conductors, size of fuses, and size 
of  control  systems  connected  to  the  module  output  are 
determined, multiply the values of short-circuit current (Isc) 

RSPSupply  -  1-888-532-2706 -  www.RSPSupply.com

http://www.RSPSupply.com/p-19710-Kyocera-KD325GX-LFB-325-watt-Solar-Panel.aspx

Summary of Contents for KD315GX-LFB

Page 1: ... the installation environment material of support structure and clamping method The PV module frame s must be attached to a support structure by one of the methods described in Section 6 INSTALLING PV MODULES Module support structures used to support the PV module s should be wind rated and approved by the appropriate local and civil codes prior to installation Do not expose the back of the module...

Page 2: ...ngs Section 12 for the permissible clamping range The clamp specification is below A SUS304 or equivalent t thickness L width a overlap 0 079 2 0mm and over min 2 76 70mm 0 098 2 5mm and over min 1 73 44mm 0 12 3 0mm and over min 1 50 38mm B anodized aluminum AL6063 T5 or equivalent t thickness L width a overlap 0 12 3 0mm and over min 2 28 58mm 0 14 3 5mm and over min 1 65 42mm 0 16 4 0mm and ove...

Page 3: ... i e two or more modules connected in series can cause a reverse voltage across the shaded cells within the module Module output current is then forced through the shaded area by the remaining illuminated cells and other PV modules in series with the partially shaded module s The current forced through the shaded cells within the PV module s causes additional module heating and severe loss of powe...

Page 4: ...46mm Weight 60 6 lb 27 5kg Mounting Hole Diameter 35 9mm Quantity 4 Grounding Hole Diameter 28 7mm Quantity 4 Application Class Class A NOTES 1 The electrical characteristics are within 5 UL verified 10 tolerance according to UL 1703 of the installed values of Pmax and within 10 of the installed values of Isc and Voc under standard test conditions irradiance of 1000W m 2 AM 1 5 spectrum and a cell...

Reviews: