background image

output. If the module faces 60 degrees away from true 
South (or North), the power loss will be 20 to 30 percent. 
When choosing a site, avoid trees, buildings or obstructions, 
which could cast shadows on PV modules especially during 
the winter season when the arc of the sun is lowest over the 
horizon. 

 

5. MODULE TILT ANGLE 

The PV modules produce more power when they are 
pointed directly at the sun. 
For grid-tie installations where the PV modules are attached 
to a permanent structure, PV modules should be tilted at an 
angle equal to the site's latitude. This will typically result in 
the highest annual energy output.

 

 

6. INSTALLING PV MODULE

 

A minimum spacing of 2” (50 mm) is required between the 
PV module and the mounting surface around the perimeter 
of PV array. The PV modules may be installed in various 
applications utilizing a variety of support structure options 
and attachment methods.

 

For optimal performance in all 

applications, clearance between the module frame and the 
mounting surface is required to allow cooler ambient air to 
circulate around the back of the module

 

and to avoid 

module and/or wiring damage. A minimum of .13” (3.2 mm) 
spacing must also be maintained between module frames 
to allow for thermal expansion.  
 
The PV modules may be attached to a support structure by 
the following methods. The structure should have enough 
strength to achieve the mounting span. When installing 
modules in a snowy area, an appropriate countermeasure 
has to be taken to prevent possible damage to the lower 
side frame by slipping snow (e.g. attach supporting parts to 
the lower side frame of modules.). Any damage caused by 
snow or such countermeasures is not covered under 
warranty. 
 

BOLTING

: Use 5/16”(8mm) stainless steel

 

(or equivalent in 

corrosion resistance) hardware through the existing .35”x.37” 
(9×9.5mm) 

slotted mounting holes in the module frame and 

then through the holes on the support structure. Tighten the 
screws with adequate torque (usually 132 in-lb; refer 
structure manufacturer specifications). Refer to the module 
drawings (Section 12) for the position of mounting holes. 
 

CLAMPING

: Fasten modules firmly using clamps which will 

not be deformed by wind load or snow load. Clamps should 
be attached to support structure with 1/4” (6mm) or larger 
bolt and nut with adequate torque (usually 71 in-lb; refer 
structure manufacturer specifications). Bolt and nut should 
be stainless steel or equivalent in corrosion resistance. 
Support structure should support the bottom of module at 
least

 

.39” (10mm) width or overlap. Clamps must not bend 

the module frame nor damage the surface of the frame. 
Clamps also must not shade the sunlight incidence on glass 
surface. Take measures to prevent module from falling off 
clamps. Refer to the ‘CLAMPING AREA’ in the Module 
drawings (Section 12) for the permissible clamping range. 
 

CONTINUOUS CLAMPING

:  

Continuous clamping means mounting PV module by two 
long clamps which cover overall length of the module frame. 

Fasten modules firmly using continuous clamps which will 
not be deformed by wind load or snow load. Support 
structure should support the bottom of module at least

 

.39” 

(10mm) overlap. Clamps must not bend the module frame 
nor damage the surface of the frame. Clamps also must not 
shade the sunlight incidence on glass surface. Take 
measures to prevent module from falling off clamps. If there 
is clearance between clamp and module side face, take 
measures to prevent module from moving or falling off (e.g. 
put plastic parts into clearance.). Refer to the 
‘CONTINUOUS CLAMPING AREA’ in the Module drawings 
(Section 12) for the permissible clamping range. 
 
The clamp specification is below; 

A- SUS304 or equivalent

t: thickness

L: width

a: overlap

0.079" (2.0mm)

 and over

min. 1.93"

(49mm)

0.098" (2.5mm)

and over

min. 1.34"

(34mm)

0.12" (3.0mm)

and over

min. 0.94"

(24mm)

Long side clamping;

min. 0.20" (5mm)

short side clamping;

min. 0.35" (9mm)

 

 

B-anodized aluminum AL6063-T5 or equivalent

t: thickness

L: width

a: overlap

0.079"

(2.0mm)

and over

frame

length

min. 0.28 "

(7mm)

0.12"

(3.0mm)

 and over

min.

1.50"

(38mm)

0.14"

 (3.5mm)

and over

min.

1.18"

(30mm)

0.16"

 (4.0mm)

 and over

min.

 0.98"

(25mm)

Long side clamping;

min. 0.20" (5mm)

Short side clamping;

min. 0.35" (9mm)

 

The clamp shape and dimensions above are for reference 
only, and any damage caused by clamps is not covered 
under warranty. 
 

7. MODULE WIRING

 

 

The PV module comes pre-wired. Each module has two #12 
AWG type PV-wire stranded sunlight resistant output 
cables each terminated with SMK R51-7/P51-7 (MC4 
compatible) connectors. The positive (+) terminal has a 
male connector while the negative (-) terminal has a female 
connector. The module wiring is solely for series 
connections only, i.e. male (+) to female (-) interconnections. 
Series and/or parallel connections shall be made with 
#10-14 AWG type PV-wire stranded output cables, having 
sunlight resistant and temperature rating of 90

 minimum, 

with SMK R51-7/P51-7 

(or MC4: PV-KST4/KBT4)

 

connectors. 

 

NOTE: 

When making connections with the connectors, 

make sure the array is disabled. 

DO NOT MAKE 

CONNECTIONS WHILE UNDER LOAD.

 Module output 

connections are marked “Do not disconnect under load”. 
 

NOTE: MAXIMUM SYSTEM VOLTAGE IS 600 VDC. 

 

The PV module and most PV system components have a 
maximum system voltage rating of 600 volts DC. Some 
grid-tie systems operate at or near this voltage rating. Like 
other polycrystalline PV modules, the open-circuit voltage 
of the PV modules increases as the ambient temperature 
decreases. Maximum system voltage is computed as the 

a

t

L

Reviews: