Kwiksol Instruction, Installation & Warranty Manual 9
I. INSTALLATION OF A SOLAR WATER HEATER SYSTEM
All systems must be installed in accordance with SANS 10106 and SANS 10254, which must
include a 400kPa Kwikot Pressure Control Valve, Kwikot Vacuum Breakers on both the cold
water supply and the hot water draw off, Kwikot Drain Cock and Kwikot 400kPa Safety Valve.
The solar water heater and solar flat plate collector panel/s or manifold for the solar
vacuum tubes must be connected by using 22mm copper piping, 22mm female Conex
fittings and/or 22mm copper elbows and tee-pieces and thermal pipe lagging.