the condensation either to the factory supplied condensate bottle, or to a drain or other 
location as required by the application. The internal pump is rated at 20 foot of head 
pressure. This means it can pump water to a maximum of 20 feet vertically. Each pump 
is equipped with an overflow safety cut-off that automatically shuts your KPHP unit 
down, sounds an audible alarm and displays a fault code (

CP

). This prevents accidental 

flooding of the conditioned space.

Condensate Tank & High Level Alarm - 

All KPHP models come standard with an 

external condensate tank. The tank is equipped with an overflow safety cut-off. When 
the tank is full, the safety will automatically shut down your KPHP systems, sound an 
audible alarm and display a fault code (

CF

) This prevents accidental flooding of the 

conditioned space. If you are using the supplied bypass plug and not using the tank this 
alarm is nonfunctional.

Service Ports - 

Located in the filter access compartment in the front of your KwiKool 

below the control panel. This gives service personal a connection point for service 
gauges to monitor the operating pressures of your KwiKool KPHP refrigeration system.

Sight Glass/Moisture Indicator - 

Located in the discharge air make up inlet. This 

feature allows operators and service personal to view the condition of the refrigerant 
returning to the evaporator coil. Used as a diagnostic tool by qualified personal.

G.

H.

I.

Page 10

VI / Application Requirements

Air Temperature Requirements Cooling -

 

The environmental requirements of 

your KwiKool unit at the installation site are 60 to 110 degrees F for the condenser 
make up air located on the front inlet on the top of the unit. 

If the unit is operated in an 

environment above 110 F 

the high pressure switch may trip, stopping the unit’s 

compressor. You also may notice diminished performance. The High Pressure Switch 
type is a manual reset. The reset switch is located in the Return Air grill filter compart-
ment. Reset the unit by pressing the button labeled HP Reset. 

Standard air-cooled 

KwiKool models are not designed to operate at temperatures below 60 degrees F. in 

cooling mode. Low-ambient temperature controls must be special ordered at an 

additional cost.

 Temperatures below 60 degrees F will cause the discharge air exhaust 

fan to cycle excessively and may damage the fan cycling switch, which requires 
qualified service personal to repair and can void your warranty.

Air Temperature Requirements Heating - 

The environmental requirements of 

your KwiKool unit at the installation site are 40 to 80 degrees F for the supply air 
located on the front of the unit. 

If the unit is operated in an environment above 80 F 

the high pressure switch may trip, stopping the unit’s compressor. You also may notice 
diminished performance. The High Pressure Switch type is a manual reset. The reset 
switch is located in the Return Air grill filter compartment. Reset the unit by pressing 
the button labeled HP Reset. 

Standard air-cooled KwiKool models are not designed to 

operate at temperatures below 40 degrees F. in heat mode. 

Temperatures below 40 

degrees F will cause the supply air fan to cycle excessively and may damage the fan 
cycling switch, which requires qualified service personal to repair and can void your 
warranty.

Capacity & Temperature Settings - 

Sizing of our units is based on matching 

capacity to a specific heat load while maintaining a 72 degree F temperature.  In order 
to maintain temperatures at 72 degrees F, the unit must have correctly sized capacity. 

B.

A.

C.

Summary of Contents for KPHP Series

Page 1: ...Portable Heat Pumps Operation Manual P P H P P H PORTABLE HEAT PUMPS...

Page 2: ......

Page 3: ...ained for future reference Section I Unit Components Page 3 Section II Assembly and Installation Page 4 6 Section III Operational Safeguards Page 6 Section IV System Operation Page 6 9 Section V Built...

Page 4: ......

Page 5: ...Unit Components Legend 1 Cold Air Return 2 Control Pad 3 Cold Air Supply 4 Condenser Air Inlet 5 Condenser Air Outlet 6 Cord Storage 7 Condensate Nipple 8 Condensate Alarm Jack 9 Access Door 10 Vent...

Page 6: ...h a float switch that shuts your KwiKool down and alerts operators with an alarm and display CF Condensate Full when the condensate tank is full This prevents accidental water overflow on the floor Th...

Page 7: ...rected normally above a drop ceiling must be well ventilated and large enough for the discharge air to be absorbed Discharge air is prevented from entering the make up air inlet by way of a factory in...

Page 8: ...C D F E G H I J Power Connection Verify that the source power phase and breaker size is compatible with your KwiKool serial plate information and that the electrical circuit is dedicated only for the...

Page 9: ...is timing out Heat Cool mode when conditioning is required in applications with changing load requirements The system automatically selects the mode based on the set point and flashes the current ope...

Page 10: ...op flashing when the ambient temperature falls below 99 degrees F HEAT If the unit was previously set to the Heat Mode then Heat will be displayed If the compressor is running Heat on the display will...

Page 11: ...by mode stays solid FAN If the unit was previously set to the fan mode then FAN will be displayed and the supply air fan will start to run Time Delay Protects your KwiKool from potential damage by del...

Page 12: ...of the unit If the unit is operated in an environment above 110 F the high pressure switch may trip stopping the unit s compressor You also may notice diminished performance The High Pressure Switch...

Page 13: ...enance Your KwiKool unit comes from the factory with air filters installed on the evaporator inlet to prevent dust and debris from entering the system and circulating in the conditioned space factory...

Page 14: ...ondensate pump Inspect condensate pump for over flow and proper operation check condensate line for a clog or crimping Resets automatically upon fault correction or call 1 800 KwiKool if the problem p...

Page 15: ...d has detected low pressure This alarm might cycle on and off Check air filter and replace if dirty Make sure nothing is blocking the filter inlet Check for icing on coil Resets automatically when fau...

Page 16: ...s installed to specification remove or add duct as needed check air filter for blockage Fault Possible Cause Possible Solution Display shows 32 and unit will not turn on cooling No connection of tempe...

Page 17: ...ed power cable and check incoming power Call 1 800 KwiKool Fault Possible Cause Possible Solution 99 Flashes on display Ambient room temperature over 99 degrees F Unit is working properly Lowering of...

Page 18: ...Revision 1017016...