EA230

 

SECTION 1 : SPECIFICATION 

Sensing Input 

Static Power Dissipation

 

  Voltage 

90 

 140 Vac @ 120 Vac 

  Max.6 watts 

   

1 phase 2 wire 

 

  Frequency 

50/60 Hz 

Under Frequency Protection (Factory Presets) 

 

  Adjustable range 45/55 Hz

 

Excitation Output

 

 

  Voltage 

Max. 100 Vdc @ power input 120 Vac 

Voltage Thermal Drift 

  Current 

Continuous 3.5A 

  Less than 3% at temperature range -40 to +70 

˚C 

   

Intermittent 5A for 10 secs. 

 

  Resistance 

Min. 15 ohms 

Environment 

  Fuse Spec. 

Slow blow 5 x 20mm UDA-8A / 250V 

  Operating Temperature  -40 to +60 

˚C 

 

  Storage Temperature 

-40 to +85 

˚C 

External Voltage Adjustment

 

  Relative Humidity 

Max. 95% 

  Max. +/- 5%  @ 1K ohm 0.5 watt potentiometer 

  Vibration 

1.5 Gs @ 5 

– 30 Hz 

 

   

5.0 Gs @ 30 

– 500 Hz 

Voltage Regulation

 

 

  Less than +/- 1% ( with 4% engine governing ) 

Dimensions 

 

  140.0 (L) x 75.0 (W) x 51.0 (H) mm

 

Build Up Voltage

 

 

  6 Vac residual volts at power input terminal 

Weight 

 

  310 g +/- 2%

 

EMI Suppression

 

 

  Internal electromagnetic interference filtering 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

ATTENTION 

1. AVR  can  be  mounted  directly  on  the 

engine,  genset,  switchgear,  control  panel, 
or  any  position  that  will  not  affects 
operation. For dimension reference, please 
see Figure 1. 

2. All voltage readings are to be taken with an 

average-reading  voltmeter  Meggers  and 
high-potential  test  equipment  must  not  be 
used.  Use  of  such  equipment  could 
damage the AVR. 

3. Terminal

"Fast-On" terminals 6.35mm (1/4 

inch) 

4. Improper 

setting 

of 

under-frequency 

protection  could  cause  the  output  voltage 
of  the  unit  to  drop  or  become  unstable 
under  with  changes  in  load.  Avoid  making 
any  changes  to  the  U/F  setting  unless 
necessary. 

 

VOLT

STAB

U/F

50.0

75.0

140.0

115.0

51.0

FUSE

8A

110V 0V E+

E-

VR

HZ

18.0

   5.8

 

Figure 1

 

Outline Drawing 

Summary of Contents for EA230

Page 1: ...anfu St Qianzhen Dist Kaohsiung City 80664 Taiwan EA230 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Leroy Somer R230 All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Page 2: ...00 Hz Voltage Regulation Less than 1 with 4 engine governing Dimensions 140 0 L x 75 0 W x 51 0 H mm Build Up Voltage 6 Vac residual volts at power input terminal Weight 310 g 2 EMI Suppression Internal electromagnetic interference filtering ATTENTION 1 AVR can be mounted directly on the engine genset switchgear control panel or any position that will not affects operation For dimension reference ...

Page 3: ...age may oscillate hunt 2 3 6 Rotated the front panel STAB control CCW until the system start oscillating and then rotate CW just past the point where oscillation occurred 2 4 System START UP 2 4 1 Perform preliminary set up as described in the above paragraphs ATTENTION The AVR reading AC voltage are all average value 2 4 2 Start prime mover and bring up to rated speed RESULT Voltage should build ...

Page 4: ...Please make sure you have read and understand the contents of the instruction manual prior to installation Incorrect wiring connection may result in irreversible damage to the product and other equipments This Automatic Voltage Regulator is not equipped with loss Sensing Protection function Over Excitation Protection An additional Over Voltage Protection device for load may be required to avoid po...

Reviews: