background image

7. 

H.SP.

 : 

Fast switching performance,   ~

Y

?

Y

:  Start-up 

For example :   

LY

 = 30, 

S  P

 = 6, 

A

    = 

I i24

 (step 4 as circular sequence)

p

In case a compensation demand for the reactive power value (K Var) is 10 times of the CK
value, the following explanations are as follows :

In  order  to  replace  the  gradual  switching  on/off  capacitor  step,  there  are  two 
solutions to an extended life of both the contactors and the capacitors as follows.

1.  Switching  on/off  the  largest  possible  capacitor  step  is  in  order  to  reduce  the 
      frequent  switching  operations.  And  the  switching  program  will  directly  start 
     entering the step in circular sequence for switching on/off capacitor if the actual
     load is fitted in with the circular sequence. Furthermore, the rest of the switching
     program should be activated in compliance with the selected        mode.

A

2. After starting this procedure, in case of the subsequent connection/ disconnection
   to capacitor again, a half of the preset switching delay time under the   

LY

 model

   will be activated; meanwhile, the decimal point of the unit place also flashes. If
      no  longer  switched  on/off  capacitor,  the  switching  delay  time  will  recover  the 
    standard setting.

p

This H.S.P. Mode will be de-activated for switching on/off capacitor if the setting
of the number of switching step is less than the switching step in circular sequence.

The controller will directly switch on the capacitor (step 4) after 30 seconds beacause the 
reactive power value (K Var) is higher than 4 times of the C/K value, thus the K Var value
in the system should be derived from the designed formula as 10-4=6. This way, the derived
value  (10-4=6)  in  K Var  is  still  higher  than  4  times  of  the  C/K  value,  a  half  of  the  preset 
switching  delay  time  under  the   

LY

  mode  will  be  activated  for  switching  on  again  (new 

default value has been automatically changed as 15s), and meanwhile, the decimal point of
the unit place also flashes.

p

Following  up  the  designed  formula,  now  the  latest  derived  value  (6-4=2)  in  K  Var  in  the 
system is less than the step 4 in circular sequence so the H.S.P. Mode should be de-activated.

Select the Auto mode, the H.S.P. Mode is de-activated.

8. 

 .  .s.

 : 

Setting of the over-voltage range : 

I i0~i30

It is no longer switched on capacitor once the measured mains supply exceeds the
preset range.

9. 

 .  .  .

 : 

Tripping setup for over voltage : 

Y

: Start-up

All  the  steps  will  be  switched off  in order once the legend 

E  2

 is shown on the 

display.
This  tripping  setting  must  be  activated  according  to the setting of the   

LY

 and 

A

    mode.

p

10. 

a.   

Auto-adjustment in inverted-phase shift    ~

Y

?

Y

:

The  phase-shift  will  be automatically reversed at 180 degrees as the measured 
phase angle exceeds 90 degrees, and the displaying screen indicates 

E  5

 after

3 seconds. Moreover,  it is  unnecessary to alternate the cable in the electrical 
network system except for the phase error.

This procedure is only applied to the following conditions.
1. The connected voltage terminals with the reverse polarity.
2. The direction of the measured current flow has been inverted.

Table of the C/K values for 380V

Table of the C/K values for 220V

KV AR

2.5

0.13

0.09

0.08

0.06

0.05

0.04

0.03

0.02

0.02

5

0.25

0.19

0.15

0.13

0.09

0.08

0.06

0.05

0.04

0.03

0.02

7.5

0.38

0.28

0.23

0.19

0.14

0.11

0.09

0.07

0.06

0.04

0.03

0.02

10

0.51

0.38

0.30

0.25

0.19

0.15

0.13

0.09

0.08

0.05

0.04

0.03

0.03

0.02

15

0.76

0.57

0.46

0.38

0.28

0.23

0.19

0.14

0.11

0.08

0.06

0.05

0.04

0.03

0.02

20

1.01

0.76

0.61

0.51

0.38

0.30

0.25

0.19

0.15

0.10

0.08

0.06

0.05

0.04

0.03

25

1.27

0.95

0.73

0.63

0.47

0.38

0.32

0.24

0.19

0.13

0.09

0.08

0.06

0.05

0.04

30

1.52

1.14

0.91

0.76

0.57

0.46

0.38

0.28

0.23

0.15

0.11

0.09

0.08

0.06

0.05

37.5

1.90

1.42

1.14

0.95

0.71

0.57

0.47

0.36

0.28

0.19

0.14

0.11

0.09

0.07

0.06

40

2.03

1.52

1.22

1.01

0.76

0.61

0.51

0.38

0.30

0.20

0.15

0.12

0.10

0.08

0.06

50

1.90

1.52

1.27

0.95

0.76

0.63

0.47

0.38

0.25

0.19

0.15

0.13

0.09

0.08

60

2.28

1.82

1.52

1.14

0.91

0.76

0.57

0.46

0.30

0.23

0.18

0.15

0.11

0.09

80

2.03

1.52

1.22

1.01

0.76

0.61

0.41

0.30

0.24

0.20

0.15

0.12

100

1.90

1.52

1.27

0.95

0.76

0.51

0.38

0.30

0.25

0.19

0.15

Ct 

150/5

200/5

250/5

300/5

400/5

500/5

600/5

800/5

1000/5

1500/5

2000/5

2500/5

3000/5

4000/5

5000/5

KV AR

2.5

0.22

0.16

0.13

0.11

0.08

0.07

0.05

0.04

0.03

0.02

5

0.44

0.33

0.26

0.22

0.16

0.13

0.11

0.08

0.07

0.04

0.03

0.03

0.02

7.5

0.66

0.49

0.39

0.33

0.25

0.20

0.16

0.12

0.10

0.07

0.05

0.04

0.03

0.02

0.02

10

0.87

0.66

0.52

0.44

0.33

0.26

0.22

0.16

0.13

0.09

0.07

0.05

0.04

0.03

0.03

15

1.31

0.98

0.79

0.66

0.49

0.39

0.33

0.25

0.20

0.13

0.10

0.08

0.07

0.05

0.04

20

1.75

1.31

1.05

0.87

0.66

0.52

0.44

0.33

0.26

0.17

0.13

0.10

0.09

0.07

0.05

25

2.19

1.64

1.31

1.09

0.82

0.66

0.55

0.41

0.33

0.22

0.16

0.13

0.11

0.08

0.07

30

1.97

1.57

1.31

0.98

0.79

0.66

0.49

0.39

0.26

0.20

016

0.13

0.10

0.08

40

2.10

1.75

1.31

1.05

0.87

0.66

0.52

0.35

0.26

0.21

0.17

0.13

0.10

50

2.19

1.64

1.31

1.09

0.82

0.66

0.44

0.33

0.26

0.22

0.16

0.13

60

1.97

1.57

1.31

0.98

0.79

0.52

0.39

0.31

0.26

0.20

0.16

80

2.10

1.75

1.31

1.05

0.70

0.52

0.42

0.35

0.26

0.21

100

2.19

1.64

1.31

0.87

0.66

0.52

0.44

0.33

0.26

Ct 

150/5

200/5

250/5

300/5

400/5

500/5

600/5

800/5

1000/5

1500/5

2000/5

2500/5

3000/5

4000/5

5000/5

Reviews: