background image

An ISO 9001:2008  Company

®

G-17, Bharat  Industrial  Estate,  T. J.  Road,  Sewree (W),  Mumbai -  400 015. INDIA.

Sales Direct.:

 022 -2 4156638,     

Tel. : 

022-241224540, 24181649,      

Fax : 

022 - 24149659

Email :

 [email protected],                                      

Website :

 www.kusamelectrical.com, 

An ISO 9001:2008  Company

®

All Specifications are subject to change without prior notice

Navin com/D:Sandeep Gupta/New Catlog Dec 2011/KM-PFR-9-06 09-12.cdr

The pioneers & leaders in high quality power factor  controllers & maximum 

demand  controllers,  now    introduce    2  new  economy  models  of  power 

factor  controllers.    These  controllers  have  microprocessors  for  automatic 

control of power  factor.   It  has digital  indication  for  power  factor.

DIGITAL INTELLIGENT POWER FACTOR 

REGULATOR

?

  Display :

 Power Factor 

?

  Simple Operation.

?

  Automatic self adjustment for C/K value.

?

  Different types of Operation sequence  (1:1:1:1….) (1:2:2:2….) (1:2:4:4….)...

     (1:4: 8...) ( 1: 1: 2 : 2 )...( 1 : 1 : 2 : 2..)...( 1 : 1 : 4 : 8..)...( 2 : 4:...( 1 - 1- 

     switching in sequential  Sequence )

?

  The set data is preserved for at least two months in the event of Power failure.

Model - KM-PFR-9-06 / KM-PFR-9-12

UNIQUE FEATURES :

SPECIFICATION 

Model KM-PFR-9-06

Model KM-PFR-9-12

No of steps

6 steps

12 steps

Voltage Burden

£

   

6 VA

 7.5VA

Operation Voltage Range

AC 220 V ± 15 % & AC 415 V ± 15 %

Input Current Range

AC 0.05 ~ 5A, max 6A

Current Burden

£

 

 0.5 VA

Power Factor Display

Digital Display, RED LED, 14.2 mm height, 0.01PF Resolution.

Power Factor Setting Range

CAP 0.90 ~ IND 0.90 ( Factory set 0.98 P.F.).

C/K setting Range

Automatic self adjustment for C / K value

Operation Time Display

10 ~ 240 sec. Delay time. ( Factory set 30 sec ).

Output contacts coils

AC 220V 5 A ( Max. AC 380 V, 5 A, typical )

Operation Temp. Range

0 ~ 60° C

Storage Temp. Range

-10 ~ 70° C

Dielectric Strength

AC 220 V, 50 Hz, 1 minute, Input / Output  / Ground

Withstanding Impulse Voltage

According to IEC 1000 - 4 - 5

Electrical Transient burst

According to IEC 1000 - 4 - 4

Connection

Plug in  Terminal block

Phase

Single Phase or Three Phase

Outside Dimension

144 x 144 mm and 65mm ( Depth) as Per Din standard 

Weight

About 1 kg

£

Reviews: