background image

05

®

®

06

Press the TEST button to turn the instrument “ON”.
The  green  LED  indicates  that  the  instrument is ON and is busy
testing. The battery is OK when the green LED is ON.

Should  the  Green  LED  not  come on while depressing the TEST 
button, replace the battery (see Battery Replacement).

If the LED (Right arrow) L1-L2-L3 is illuminated, clockwise rotary
field is present.

If the LED (Left arrow) L1-L2-L3 is illuminated, a counter clockwise
rotary field is present.

Please note that; the phase control is displayed even if the neutral
conductor N is connected instead of L1, L2 or L3.

Also refer to table (as indicated on the back of instrument)

Determination of motor connections and rotation of motor

Connect test leads to instrument and to the motor connections.
These are also Color Coded;
U  = Red                           which connects to L1 on the tester.
V  = White (or yellow)       which connects to L2 on the tester.
W = Blue (or black)           which connects to L3 on the tester.
Press  button  On.  The green LED indicated that the instrument is
ready for testing.
Turn the motor shaft by at least half rotation towards the right. Look 
at the Leds while doing that.

It is important to ensure that the user looks from the front side onto
the driving shaft and the front side of the tester at the same time, so
that motor rotation can be confirmed.

The  red  LED  (Right  arrow)  L1-L2-L3  indicated  clockwise  motor
rotation if the lines are connected as follows : L1 to U, L2 to V, L3 to
W.

The  red  LED  (Left  arrow)  L1-L2-L3  indicates  counter-clockwise
motor  rotation  if  the lines are connected as follows : L1 to V, L2 to 
U, L3 to W.

FRONT PANEL LAYOUT :

KM 888 PMR

®

L1

L2

L3

R U

S V

T W

TEST

BAT

OK

C

CAT.III 600V

L2 L1 L3

L1 L2 L3

PHASE PRESENCE INDICATOR

PHASE ROTATION TESTER

MOTOR ROTATION TESTER

MOTOR ROTATION DETERMINED WHILE

USER FACING (looking at) MOTOR SHAFT

Connect L1, L2 and L3 to their respective

Phase. Their corresponding Lamp will

light up when power (>120Vac) is present.

Depress the TEST button, The Led L1L2L3

will indicate clockwise phase rotation.

If anti-clockwise phase rotation is

present, the Led L2L1L3 will light up.

Connect L1 from tester to U of motor.
Connect L2 from tester to V of motor.

Connect L3 from tester to W of motor.

Turn the motor shaft by at least half a turn

clockwise (towards the right)

Depress the TEST button,

L1L2L3 = clockwise motor rotation.

L2L1L3 = anti-clockwise motor rotation.

Summary of Contents for KM 888PMR

Page 1: ...ai 400 015 INDIA Sales Direct 022 24156638 Tel 022 24124540 24181649 Fax 022 24149659 Email kusam_meco vsnl net Website www kusamelectrical com www kusam meco co in AN ISO 9001 2008 COMPANY MODEL KM 888PMR PHASE MOTOR ROTATION INDICATOR OPERATION MANUAL ...

Page 2: ... SAFETY CHECKS DON T TOUCH GENERAL DESCRIPTION BRIEF PRODUCT DESCRIPTION OPERATING INSTRUCTIONS FRONT PANEL LAYOUT PRINCIPLE OF HOW IT WORK PREPARATION FOR USE REPLACING THE BATTERIES FUSE REPLACEMENT SPECIFICATIONS TEST CERTIFICATE WARRANTY 01 02 02 03 04 04 06 07 08 08 08 09 10 11 ...

Page 3: ...hand to hand contact between the tester and extended test leads When using the tester with test leads ensure that they are safe and properly authorized Disconnect the tester from any external circuit when changing the batteries CAUTION READ THE MANUAL Follow the instructions in the Manual for every measurement Read and understand the general instructions before attempting to use this tester SAFETY...

Page 4: ... winding is connected to the terminals of the Motor when the rotation Leds light up BRIEF PRODUCT DESCRIPTION This 3 Phases and Motor Rotation Tester has 3 test leads which connects to the 4 mm female sockets on the tester on the one side These Test leads are color coded L1 Red which connects to L1 on the tester L2 White or yellow which connects to L2 on the tester L3 Blue or black which connects ...

Page 5: ...ght Look at the Leds while doing that It is important to ensure that the user looks from the front side onto the driving shaft and the front side of the tester at the same time so that motor rotation can be confirmed The red LED Right arrow L1 L2 L3 indicated clockwise motor rotation if the lines are connected as follows L1 to U L2 to V L3 to W The red LED Left arrow L1 L2 L3 indicates counter clo...

Page 6: ... the battery voltage is below the threshold the LED will not light up thus replacing the battery indication PREPARATION FOR USE Fuses In doubt check the fuses using a ohm meter Please note that this instrument will not indicate anything should the fuses be blown Test Leads Check the test leads for defects or cracks Replace if cracked or damaged Only replace with the same type Cleaning Clean the in...

Page 7: ...n Over Load 550V between all terminals Frequency Range Class III 600V towards Ground Fuses 5 20 mm 200mA 250V fuse General Battery 9V IEC 6LR61 Current Consumption Max 18 mA Ground MECHANICAL Size 151 72 35 mm Material Poly carbonate ABS Weight less carrying case 120g with batteries Display Neon Lamps and LEDs ENVIRONMENTAL Operating temperature Range 15ºC to 55ºC Storage Temperature 20ºC to 70ºC ...

Page 8: ...horized dealer shall extend this warranty on new and unused products to end user customers only but have no authority to extend a greater or different warranty on behalf of KUSAM MECO KUSAM MECO s warranty obligation is limited at option free of charge repair or replacement of a defective product which is returned to a KUSAM MECO authorized service center within the warranty period THIS WARRANTY I...