6.  RCCB / ELCB Testing - Sensitivity-

* - Instantaneous
  - Time Delay

1 - Instantaneous
2- Time Delay

Push Select to change Selection
to instantaneous, then press “TEST”

Press 1 to select Instantaneous

Turn Instrument “ON” by pressing the “ON” button.
The L.C.D. Display will come to the following Screen.

KM 2820 EL

KM 2821 EL

Dial Starting 

Current.  123mA

Enter Starting

Current.  123mA

Dial the Starting Current of the
Instantaneous Test using the Knob.

Enter the Starting Current for the
Test using the Keypad.

Positive
Start Edge

Select the positive or Negative 
Start Edge using the Select Button.

Negative
Start Edge

0

180

Select the positive or Negative 
Start Edge using any Number Button.

Connect Leads

to Earth & Phase

Connect Leads to Earth and Phase.
The Test will start Automatically.

Connect Leads

to Earth & Phase

V=317V
I=127mA

Test in Progress.  The Voltage

between leads is 317V and I=127mA

V=317V
I=127mA

V=317V -
I=140mA Hold

g

TRP

TRP=

Tripped, Display on Hold

at 140mA, Tripped on 

-

 edge of signal

V=317V
I=999mA Hold

g

OVR

OVR=

OverRange Display on Hold

at 999mA, Did not trip.

7.  RCCB / ELCB Testing - Time Delay-

- Instantaneous

*- Time Delay

1 - Instantaneous
2- Time Delay

Push Select to change Selection
to Time Delay, then press “TEST”

Press 2 to select Time Delay

Turn Instrument “ON” by pressing the “ON” button.
The L.C.D. Display will come to the following Screen.

KM 2820 EL

KM 2821 EL

Dial Testing

Current.  125mA

Enter Testing

Current.  125mA

Dial the Testing Current of the
Instantaneous Test using the Knob.

Enter the Testing Current for the
Test using the Keypad.

Positive
Start Edge

Select the Positive or Negative 
Start Edge using the Select Button.

Negative
Start Edge

0

180

Select the Positive or Negative 
Start Edge using any Number Button.

Connect Leads

to Earth & Phase

Connect Leads to Earth and Phase.
The Test will start Automatically.

Connect Leads

to Earth & Phase

V=317V    T=4.023s
I=125mA

Test in Progress since 4.023s.  The Voltage

between leads is 317V and Constant current is 125mA

V=317V    T= 4.023s
I=125mA

V=317V +  T=12.435s
I=125mA Hold

g

TRP

TRP=

Tripped, Display on Hold

at 12.435s, Tripped on 

+

 edge of signal

V=317V   T=99.999s
I=125mA Hold

g

OVR

OVR=

OverRange Display on 

Hold

at 99.999s, Did not trip.

6

7

Summary of Contents for KM 2820EL

Page 1: ...ter Digital AC AC DC Clampmeter AC Clamp Adaptor AC DC Current Adaptor Thermo Anemometer Thermo Hygrometer Distance Meter Digital Lux Meter Network Cable Tester Power Factor Regulator Earth Resistance...

Page 2: ...any sign of abnormality or damage If any abnormal conditions exist broken test leads cracked case display faulty etc Do not attempt to take any measurement or use the tester Return your Digital RCCB...

Page 3: ...itive or Negative Phase 2 SPECIFICATIONS Functions KM 2820EL KM 2821EL Current Settings Current Selection Phase Start Selection 0 180 Phase Polarity Trip Indicator Operating Voltage L E Timer Resoluti...

Page 4: ...4 1 2 3 1 On Switch Test Button Switch 2 Selection Switch 0 180 Switch 3 Current Selection Knob 4 L C D DIGITAL EARTH LEAKAGE TESTER Microprocessor Controlled KM 2821EL Press TEST Multi Voltage Auto...

Page 5: ...999mA HoldgOVR OVR OverRange Display on Hold at 999mA Did not trip 7 RCCB ELCB Testing Time Delay Instantaneous Time Delay 1 Instantaneous 2 Time Delay Push Select to change Selection to Time Delay th...

Page 6: ...lace the fuse located under the Battery holder Only replace with the same specification fuse 2A Fast Blow 11 Servicing and Calibration Your Digital RCCB ELCB tester has been factory Calibrated However...

Page 7: ...a KUSAM MECO authorized dealer This warranty does not apply for damaged Ic s fuses disposable batteries carrying case test leads or to any product which in KUSAM MECO s opinion has been misused altere...

Reviews: