All Specifications are subject to change without prior notice
D:\Chhaya\My Documents\Chhaya\backup\catlog\New Cat\KM 1320-3000B.cdr
?
Measuring Times :
Over 5000 times (Short-circuit test, interval time should be at least 30 seconds)
?
RS232 Interface :
RS232 interface, software supervision, storage data can be uploaded to
computer, saved or printed.
?
Communication Wire :
One piece of RS232 communication wire, with length 1.5m
?
Data Storage :
300 sets, “MEM” icon storage indicator, flash display “FULL” icon to indicate storage is full
?
Data Hold :
Data hold function: “HOLD” icon display
?
Data Access :
Data read function: “READ” icon display
?
Overflow Display :
Exceeding measuring range overflow function: “OL” icon display
?
Interference Test :
Recognize interference signal automatically, “NOISE” icon display when interference
voltage exceed 5V
?
Auxiliary Earthing Test :
Can measure auxiliary earth resistance, 0.00K
Ω-30
k
Ω(100
R+rC<50k
Ω, 100
R+rP<50k
Ω)
?
Operating Temperature & Humidity :
-10
?
-40
?
, below 80%rh
?
Storage temperature & humidity :
-20
?
-60
?
, below 70%rh
?
Alarm Function :
When measuring value exceeds alarm setting value, there is alarm Sound
?
Battery Voltage :
When battery voltage decreases to about 7.5V, battery voltage low icon will display,
reminding to replace battery.
?
Overload Protection :
Measuring earth resistance: between each interfaces of C(H)-E
、
P(S)-ES,
AC 280V/3 seconds
?
Insulation Resistance :
Over 20M
Ω (
between circuit and enclosure it is 500V)
?
Withstanding Voltage :
AC 3700V/rms (Between circuit and enclosure)
?
Electromagnetic Features :
IEC61326(EMC)
?
Protection Type :
IEC61010-1 (CAT
Ⅲ 300
V
、
CAT IV 150V
、
Pollution 2), IEC61010-031, IEC61557-1
(Earth resistance), IEC61557-5 (Soil resistivity), JJG 366-2004
?
Power Consumption :
Standby: about 20mA (Backlight shut off)
Boot and with backlight: about 45mA (25mA without backlight)
Measurement: about 100mA (Backlight shut off)
?
Power Supply :
DC 9V(Zi-Mn dry battery R14S 1.5V 6 PCS, continuous standby for 300 hours )
?
Weight :
4.5kg (including package)
?
Dimension :
215(L)×190(W)×95(H)mm
?
Accessories :
Standard testing wire 4nos., Simple testing wire 2nos., earth rods 4pcs., Battery, Manual
Software CD, RS232 Communication cable & Carrying case.
ELECTRICAL SPECIFICATIONS :
a
>20
h
a
>20
h
1. Base Conditions and Working Conditions
Influence Quantity
Working Conditions
Base Condition
Ambient Temp
23°C±1°C
Ambient Humidity
40%-60%
Working Voltage
9V±0.1V
9V±1.5V
<80%
-10°C-40°C
Auxiliary Earth Resistance
<100Ω
<30
k
Ω
Interference Voltage
no
<20
V
Interference Current
no
<2
A
Electrode Distance
when measuring R
a
>5
d
a
>5
d
Electrode Distance
when measuring
ρ