Kuno Engels ENGELAIR ELW 170 Manual Download Page 2

Manual ELW 170 / ELW 180                                                                                 

May 2020 

page 2 

 
 
 
The housing may be opened to be connected to the electricity supply and to set parameters.  
There are hazardous circuits inside the housing. The airflow monitor may only be operated  
by staff who have been authorised and trained to do so by the system operator.  
The applicable standards and directives should be observed.  
The EMC directives must be ensured for the entire system.  
 
 

 

 

 

 

2. Proper use  
 

The airflow monitors ELW 170 and ELW 180 are only intended for commercial use.  
The devices are used for the following purposes: 

To evaluate airflows and the resultant generation of switching statuses.  

For monitoring off ans or butterfly valves 

For use in conjunction with DDC systems 

For flow –dependent monitoring of humidifiers and electric heating coils in accordance with 
DIN VDE 0100-420 (Oct. 2019). Please also observe our information S 20. 

Proper use also includes the following points: 

The directions provided in these instructions must be noted and followed. 

The technical limit values (see Chapter 6 “Technical data”) must be observed.    

The sensor should only be used to measure air.  

The devices are not suitable for use in areas at risk of explosion or pressurised areas. 

The manufacturer accepts no liability for damage resulting from the device not being used properly,  
unauthorised modifications to the device, failure to observe these instructions and deployment of  
staff who are not qualified. The manufacturer’s guarantee also ceases to apply in such instances. 

 
 
 

3. Standards and directives  
 

The device complies with the following requirements: 

2014/30/EU EMC directive  

2014/35/EU Low Voltage Directive   

EN 61326-1:2013 General EMC requirements  

EN 61326-2-3:2013 Immunity for residential, commercial and light-industrial environments   

DIN EN 60947-5-1 Low-voltage switchgear and controlgear  

EN 50581:2012 Restriction of hazardous substances 

 
 

4. Structure of the measurement system  
 

The measurement system comprises the sensor and control unit. The measurement system is available in 
two different designs: 

ELW 170 for wall mounting (sensor is connected using a cable)  

ELW 180 for duct mounting (sensor is permanently connected to the control unit)  

Sensor and control unit are calibrated independently and, in the version for wall mounting, can be replaced 
with identical devices at any time. Sensors and control devices are not compatible with the foreign ELW line. 

 
 

5. Principle of operation  
 

The airflow monitor works in line with the calorimetric measuring principle where the amount of heat removed  
by the airflow is measured and converted into the switching value. In order to do this, the sensor contains a 
heating element and 2 temperature sensors. A microcontroller controls the heating and measures differences  
in temperature. On the basis of stored calibration curves, it calculates the speed of airflow and transfers the 
value to the control unit in a serial manner. Here another microcontroller determines the switching behaviour  
of the two relays from the setpoint values for the controller.  

 
 
 
 

Summary of Contents for ENGELAIR ELW 170

Page 1: ...patents utility models or registered design The following warning notices are used in these instructions Immediate danger from electrical voltage and current Failure to heed the information indicated...

Page 2: ...re not qualified The manufacturer s guarantee also ceases to apply in such instances 3 Standards and directives The device complies with the following requirements 2014 30 EU EMC directive 2014 35 EU...

Page 3: ...e matched to one another according to the standards and specifications applicable locally The 2x2 pin terminal block for the rated voltage and the two 3 pin terminal blocks for the potential free rela...

Page 4: ...and inductions The maximum permitted sensor cable length is 30 m Ensure that the four cables are connected correctly so that the Sensor or control electronics are not damaged 6 2 3 Connecting the swit...

Page 5: ...s Factory setting 15 seconds 7 2 2 Switch off delay speed controller Allows the switch off delay to be set to between 2 and 20 seconds Factory setting 2 seconds 7 2 3 Hysteresis speed controller Allow...

Page 6: ...e 100 240V AC or 24V 10 AC DC Rated consumption 3 VA Contact 2 two way contacts potential free Switching voltage max 250 V AC Switching current max 8 A Electric connection 2 5 mm sensor 1 0 mm screw t...

Page 7: ...t The device should be stored in line with the ambient conditions specified in the technical data 13 Disposal When disposing of device be sure to separate the materials and recycle the device componen...