9. 

Operating modes 

9.1. 

Off operating mode 

The O

FF 

position is automatically selected (reset function) during the application of battery  voltage in 

order to prevent the triggering of an unintentional start-up. When switching to O

FF 

from another operat-

ing mode: 

  a genset operation is immediately ended 

  previously displayed error messages, except the fault messages 9 and 10, are deleted as long as 

their alarm contact is still active 

  the automatic system is unlocked. However, if the Q

UICK 

S

TOP 

(E

MERGENCY 

S

TOP

)

 

input is still ac-

tive, unlocking is not possible; the 

AUTOMATIC SYSTEM LOCKED

 message remains. 

9.2. 

Manual operating mode 

The 

START CONTROL

 indication flashes as long as there is no start release and the 

SWITCH ON AUXILIARY 

DRIVES

 signal is present. If no auxiliary drives are required (for start release), terminal 8 from X2, 

START 

RELEASE

 should be switched with L-. The motor can be started using the S

TART

 key. If the generator 

voltage lies within the nominal ranges with its voltage and frequency values, the generator can be 
switched on with the G

EN

-O

N

 (

I

) key or off again with the G

EN

-O

FF

 (

O

) key. The actuation of the O

key remains ineffective if the generator voltage does not lie within the specified limits. 
All switching processes are only carried out manually and not automatically. Even a remote start order 
does not lead to the automatic switch-on of the generator. In order to switch off the genset, the O

FF 

or 

(in the event of the remote start command being missing) A

UTOMATIC 

operating mode must be select-

ed. 

9.3. 

Auto operating mode 

After  the  external  start  command  is  present  the  genset  will  be  started  after  the  parameterised  delay 
time has elapsed. The 

START  CONTROL

 indication flashes as long as there  is no  start release and the 

SWITCH ON AUXILIARY DRIVES

 signal is present. If no auxiliary drives are required (for start release), ter-

minal 8 from X2, 

START RELEASE

 should be switched with L-. If the genset has not started at the end of 

the starting program, the 

FAILED START 

/

 MOTOR FAULT

 alarm is issued and the automatic system inhibit-

ed.  After  the  start-up  of  the  genset,  the  generator  is  switched  on  as  soon  as  the  nominal  generator 
voltage and frequency are reached. 
After removal of the start command, the generator is switched off immediately. In order to prevent heat 
build-up, if it was loaded the genset continues to run without load for the run-on time set and then is 
shut down. 
In addition to the remote start, the genset can also be started via the Sprinkler command (see further 
in this document). 

9.4. 

Test operating mode 

After button selection to the T

EST 

position, the start program is triggered. The 

START  CONTROL

 indica-

tion flashes as long as there is no start release and the 

SWITCH ON AUXILIARY DRIVES

 signal is present. If 

no  auxiliary  drives  are  required  (for  start  release),  terminal  8  from  X2, 

START  RELEASE

  should  be 

switched with L-.  
If  the  generator  voltage  lies  within  the  nominal  values  parameterised  with  its  voltage  and  frequency 
values, the generator can be switched on with the G

EN

-O

N

 (

I

) key or off with the G

EN

-O

FF

 (

O

) key. 

If a remote start command occurs during test operation, the system switches to generator operation. 
Then, it is not possible to manually switch off the generator circuit breaker. A manual operation of the 
switch is only possible after the remote start command has been withdrawn. 
In order to switch off the genset, the  O

FF 

or (if the remote start command is not present)  A

UTOMATIC 

operating mode must be selected. 

Summary of Contents for KEA 292 INS

Page 1: ...d the parameters can be set with a PC Because the KEA 292 has the same dimensions and fastenings as its predecessor replacement is simple Ten parameterisable alarm and operating indicators which can b...

Page 2: ...9 5 Sprinkler operation 7 10 Error messages Programmable operation indicators 7 10 1 Use as an operational indicator 7 10 2 Use as an error message 7 10 3 Alarms 9 and 10 7 10 4 Internal error message...

Page 3: ...set via a USB inter face The PARAWIN software is required for this All relevant values and signals can be read out via an add on module The device is delivered with standard parameterisation and labe...

Page 4: ...w can be selected using the keys 7 2 Start key The motor can be started in MANUALoperating mode by actuating this button If the motor needs to be preheated the pre heating device must be externally co...

Page 5: ...out as soon as the genset exceeds the ignition speed during start up recognised through the D signal of the generator through the speed sensor signal or through the generator voltage in accord ance w...

Page 6: ...be select ed 9 3 Auto operating mode After the external start command is present the genset will be started after the parameterised delay time has elapsed The START CONTROL indication flashes as long...

Page 7: ...of the 10 LEDs can either display an error message or be parameterised as an operation indica tors 10 1 Use as an operational indicator These displays are independent of the selected operating mode T...

Page 8: ...et can immediately switch to generator operation in the event of a start request sprinkler request 10 4 5 Generator circuit breaker tripped The alarm is internally controlled if no generator feedback...

Page 9: ...display remains switched on 14 Start program 14 1 Start process diesel engine 1 Start delay 2 sec 2 Starter on for 10 sec 3 Pause 7 sec 4 3 start attempts 5 6 start attempts for sprinkler operation 6...

Page 10: ...puts 2 phase generator voltage monitor for nominal voltage 400 V adjustable in 1 Volt steps Adjustable 250 480 Volt Generator frequency 45 to 65 Hz adjustable in 0 01 Hz steps from 40 to 70 Hz Battery...

Page 11: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Page 12: ...INS_EN_Ver 2016 07 01 doc 12 Alfred Kuhse GmbH Telephone 49 4171 798 0 E mail kuhse kuhse de Subject to technical changes An der Kleinbahn 39 21423 Winsen Fax 49 0 4171 798 117 http www kuhse de 16 2...

Page 13: ...___________________________________________________________________________ _____ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Wins...

Reviews: