13.
Start program
13.1.
Start process, diesel engine
Start delay 2 sec.
Starter on for 10 sec.
Pause 7 sec.
3 start attempts
6 start attempts for sprinkler operation
Delay
MONITORING ON
7 sec.
Switch-back delay 60 sec.
Idle time 180 sec.
Sprinkler operation run-on time 600 sec.
Stop time 30 sec.
13.2.
Start process, gas engine
Starter on
If the starter speed is exceeded, the switching-on of the ignition is delayed (e.g. after 2 sec.)
Then (another 2 sec.) open gas solenoid valve
Starter now on for another 7 seconds
Then close gas solenoid valve
Starter off
Ignition off after 6 sec.
New start sequence after 1 sec.
The parameterised standard values for a diesel engine are specified here. If diesel engines with preheat-
ing systems are used, an external preheating button must be provided in the M
ANUAL
selector switch posi-
tion. The start delay serves as a preheating time during automatic starts.