Operating instructions 

Automatic start/stop system for emergency gensets 

For product: KEA 291 NSTR 

File: 

BA_KEA 291 

NSTR_EN_Ver

 2015-03-20

 (Replaces ver. 12-09-24) 

1.

Use and basic operation

The KEA 291 NSTR automatic system is used in 

emergency power systems

The function of the output relays and the parameters can be set with a PC. 

Because the KEA 291 has the same dimensions and fastenings as its predecessor, 

replacement

 is 

simple. 

Ten parameterisable alarm and operating indicators 

– which can be labelled by easily 

replaceable paper strips 

– as well as 

four

 

general displays 

are displayed through LEDs. The pa-

rameterisation can be performed using the 

serial USB interface

 with the 

P

ARA

W

IN 

parameterisation 

program. 

Important note!

 

The operation of the automatic system is simple and uncomplicated as it is carried out via the usual 
buttons 

– without menu guidance – as for all previous automatic systems. 

2.

Revision history

Created 

Changed 

Version 

12-09-24

First edition 

12-09-24

15/01/2015 

Connection diagrams updated, layout changed, drawings renewed  

2015-03-
20 

2015-08-28 

Technical data: 1. Removed "for coupling onto an add-on module" (serial 
interface) 2. Options in preparation: RS-485 int GSM modem 
Scale drilling template inserted. 

2015-03-
20 

Summary of Contents for KEA 291 NSTR

Page 1: ...parameterisable alarm and operating indicators which can be labelled by easily replaceable paper strips as well as four general displays are displayed through LEDs The pa rameterisation can be perform...

Page 2: ...e 6 8 4 Mains circuit breaker tripping 7 8 5 Test operating mode 7 8 6 Sprinkler operation 7 9 Error messages Programmable operation indicators 8 9 1 Use as an operational indicator 8 9 2 Use as an er...

Page 3: ...his also applies for all relays and inductances that are used differently in the switchgear or are externally controlled 5 General description The KEA 291 NSTR automatic system is a further developmen...

Page 4: ...ng mode is prevented The operating modes described below can be selected using the keys 6 1 Start key The motor can be started in MANUAL operating mode by actuating this button If the motor needs to b...

Page 5: ...ion speed during start up recognised through the D signal of the generator through the speed sensor signal or through the generator voltage in accordance with the parameterisation Switching on the sta...

Page 6: ...art command does not lead to automatic switch on of the generator Also the mains is not automatical ly switched on if an error message occurs during generator operation e g GENERATOR OVERCURRENT which...

Page 7: ...mote start command occurs operation switches over to generator operation Then it is not possi ble to manually switch off the generator circuit breaker Manual operation of the switch is only pos sible...

Page 8: ...m is locked The parameterisation is described in the service instructions 9 3 Alarms 9 and 10 Both these alarms can be delayed from 0 to 240 sec by the signal transmission i e for the alarm contact to...

Page 9: ...tch on duration of the stop solenoid the stop process is repeated and the FAILED START MOTOR ERROR message is displayed The automatic system is not locked so that the genset can immediately switch to...

Page 10: ...sec Idle time 180 sec Sprinkler operation run on time 600 sec Stop time 30 sec 13 2 Start process gas engine Starter on If the starter speed is exceeded the switching on of the ignition is delayed e...

Page 11: ...UNDERVOLTAGE display is actuated in the event of a disrupted rotating field Adjustable switching points 50 300 Volt Mains frequency 45 to 65 Hz adjustable in 0 01 Hz steps from 40 to 70 Hz 2 phase gen...

Page 12: ...STR_EN_Ver 2015 03 20_EN doc 12 14 12 Alfred Kuhse GmbH Telephone 49 4171 798 0 E mail kuhse kuhse de Subject to technical changes An der Kleinbahn 39 21423 Winsen Fax 49 0 4171 798 117 http www kuhse...

Page 13: ...20_EN doc 13 14 ______________________________________________________________________________________ Alfred Kuhse GmbH Telefon 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Klein...

Page 14: ...hse GmbH Telefon 49 4171 798 0 kuhse kuhse de Technische nderungen vorbehalten An der Kleinbahn 39 D 21423 Winsen Luhe Telefax 49 4171 798 117 www kuhse de 14 14 Operating instructions for KEA 252 PA...

Reviews: