KUHNKE Automation
21
5.4 Output Channel Terminals, X1 … X6
Connector
3-pin, male, up to 6 mm
2
, Connector included in package
Use male connector SPC 5/ 3-ST-7.62 (1996029)
Max. lead length to consumer location: 30m
The operation of the Power Heat Controller without
connectors X1 ... X6 (6 pieces) is prohibited.
X1
Phase
PC 4 HV/ 3-ST-7.62
1
L2
Channel 1.1
2
Channel 2.1
3
Channel 3.1
X2
Phase
PC 4 HV/ 3-ST-7.62
1
L1
Channel 1.2
2
Channel 2.2
3
Channel 3.2
X3
Phase
PC 4 HV/ 3-ST-7.62
1
L3
Channel 4.1
2
Channel 5.1
3
Channel 6.1
X4
Phase
PC 4 HV/ 3-ST-7.62
1
L2
Channel 4.2
2
Channel 5.2
3
Channel 6.2
X5
Phase
PC 4 HV/ 3-ST-7.62
1
L1
Channel 7.1
2
Channel 8.1
3
Channel 9.1
X6
Phase
PC 4 HV/ 3-ST-7.62
1
L3
Channel 7.2
2
Channel 8.2
3
Channel 9.2
The lead connecting the consumer and the thermo-controller to be no longer
than 30 m.