13
(1)
Exciting Amperage
Amperage fluctuates based upon the winding temperature. Following is for reference
only
.
Frequency/Rated Output
Load
Exciting Amperage
(Measured)
Single-Phase 60Hz: 12 kW
No load
1.1A
Full load
( power factor=1.0)
1.5A
(2)
Resistance Value
Nominal resistance of the winding is tolerated
within
± 10% at 20
℃
of the ambient
temperature. The resistance must be measured by low resistance tester. It cannot be
measured by multi-purpose tester due to index error.
Measurement value (Ω
)
Main Stator
Exciter Stator
Rotor
1
2
3
4
5
Armature
Exciter
Winding
J
-
K
Exciter Field
Armature
Between
U-W
A – B
B – C
C – D
-
-
-
0.14Ω
0.29Ω
5.8Ω
8.60Ω
0.83Ω
(B)
(W)
(R)
(G)
(Y)
(Br)
(L)
(Or)
(Gr)
(Vi)
Black
White
Red
Green
Yellow Brown
Blue
Orange
Gray
Violet
Summary of Contents for D902-E4B
Page 1: ...File DGO 442_GL14000 USA SERVICE MANUAL GL14000 USA ...
Page 8: ...5 4 General 4 1 Dimension Unit below is shown by mm ...
Page 9: ...6 ...
Page 10: ...7 5 General Parts Description 5 1 Serial Number Unit Serial Number Engine Serial Number ...
Page 11: ...8 5 2 Main Components ...
Page 30: ...10 Wiring Diagram 27 ...
Page 31: ...28 ...