3.8
Control-Output (Option)
Four control outputs are available at terminal 20, 21, 22 and 23.
Switching conditions can be set in the PRESELECTION MENU. The output Ctrl. Out 1 – 4 are fast PNP
outputs with a switching capability of 5 – 30 Volt / 200 mA per channel. The switching states is
displayed (display with unit and status bar) as C1 … C4.
The switching voltage of the outputs must be applied to input terminal 19 (COM+).
In case of switching inductive loads it is advisable to use external filtering of the coils. The switching
states is displayed (display with unit and status bar) as C1 and C4.
Wiring of the control-outputs:
3.9
AC Power supply (Option)
The unit accepts AC supply from 115 to 230 V at the terminals 24 and 25. The power consumption
depends on the level of the supply voltage with approx. 3VA and the additional current required at the
auxiliary voltage output.
Devices with option AC can also be supplied with a DC voltage between 18 and 30 VDC at terminals 1