Mounting and Operating Instructions 

Optical fiber transmitter modules: LWLS.1, LWLS.2, LWLS.4, LWLS.5 
Optical fiber receiver modules: LWLE.1, LWLE.4, LWLE.5 
 
 

Product description 

The optical fiber modules LWLS and LWLE form together a transmission system for data 
transmission of industrial signals by means of optical fibers. 
Both transmitter and receiver modules have four channels, which are completely independent of 
each other, with differential inputs and outputs. All four channels allow the transmission of signals 
with a maximum data rate of 800 kbit/s. With their technical features, the optical fiber modules are 
intended for the transmission of signals from incremental encoders.  
The modules are available in various level and supply voltage variants: 

 

 

 

Differential signals with RS422 or Push-pull HTL levels from other sources may also be connected to these devices. 
The optical fiber modules are mainly used when signals are to be transmitted in environments with strong interferences 
or when, due to high ground potential differences between the signal source and the signal processing equipment, 
potential separation is necessary.  
High ground potential differences generally appear also in case of large distances between the encoder and the PLC or 
any other processing electronics. 
The optical fiber cable is failure-safe: it does not constitute any danger in case of damage. Since the light-emitting 
component used is not a laser, but a light-emitting diode, the transmission line is totally safe, even when looking directly 
into the opened connector or into the broken glass fiber.  
The optical fiber cable can be routed through explosive areas. 
If necessary, a level conversion can be linked with the potential separation without problem. Since all devices use the 
same signal transmission protocol on the optical fiber cable, any transmitter can be combined with any receiver. 
 

Approved purpose 

The local standards, directives, provisions and regulations must be adhered to. The installation of the devices can only 
be performed by a competent staff trained to that end. The modules must be protected against humidity during storage 
and transportation. They shall not be used outside of the ranges specified in the technical data. 
 
 

Technical characteristics 

Designation 

Characteristic 

Construction  

Housing for DIN rail mounting acc. to EN 50 022 

Dimensions (W x L  H) 

22.5 x 110.8 x 88.4 mm 

[0.89 x 4.36 x 3.48“] 

Protection 

IP40, terminals IP20 

Optical fiber connection 

ST connector, 13 mm, 

 9 mm, 

on the bottom side of the housing 

Terminals 

Protected against contact, max. conductor diameter: 2.5 mm

Glass fiber 

Multimode fiber, 50/125 µm, 62.5/125 µm 

Max. optical transmission distance 

2000 m 

Optical fiber synchronisation display 

LED is on when the synchronisation is set and blinks when the 
synchronisation is lost or the optical fiber cable is broken 

Input signals sampling rate 

10 MSamples/s 

Supply voltage 

10 

… 30 V DC or 5 V DC ± 5% 

Power consumption per module 

< 2 W 

Operating voltage 
reverse connection protection 

available 

Electrical inputs of the transmitter and 
electrical outputs of the receiver  

Channels A, B, 0 (C), D with inputs and outputs 
A, /A; B, /B, 0 (C), /0 (/C) and D, /D 

Order code 
 

Level 

Port 

Supply voltage 

6.LWLS.1

 

RS422 

Input 

10 … 30 V DC 

6.LWLS.2 

HTL, Push-pull 

Input (w.o. inv.) 

10 … 30 V DC 

6.LWLS.4

 

RS422 

Input 

5 V DC ± 5% 

6.LWLS.5

 

HTL, Push-pull 

Input 

10 … 30 V DC 

6.LWLE.1

 

RS422 

Output 

10 … 30 V DC 

6.LWLE.4

 

RS422 

Output 

5 V DC ± 5% 

6.LWLE.5

 

HTL, Push-pull 

Output 

10 … 30 V DC 

E

ng

li

sh

 