7. DIAGNOSTIC & TROUBLES AND CORRECTING MEASURES   

As  soon  as  you  power  on  this  product,  it  starts  self-diagnosis  function  and  show  you  the  result,  so  it 

help you not to perform a failure due to the initial system errors.   

When you need to perform self-diagnosis function, just push the 'RESET' button, then it will show you 

the diagnosis results. (Note : Do not push 'RESET' button while the system operate). Error messages and 

trouble shooting methods of diagnosis results are explained as follows.   

 

No 

Error Message 

Probable causes 

Corrective measures 

 E E P r

 

 EEPROM Fault 

 EEPROM (IC13) Fault 

 EEPROM (IC13) Exchange 

  

  

 Internal Circuit Fault 

 Circuit check or Exchange 

 E r r P

 

 Internal Voltage Fault (+5V) 

 Internal Overvoltage 

 Inspect & Adjust (VR1) 

 Power Line Short or Broken 

 Power Line Check 

 Internal Circuit Fault 

 Circuit check or Exchange 

 E  P5

 

 Internal Voltage Fault (+5V) 

 Internal Overvoltage 

 Inspect & Adjust (VR1) 

 Power Line Short or Broken 

 Power Line Check 

 Internal Circuit Fault 

 Circuit check or Exchange 

 E P 1 2

 

 Internal Voltage Fault (+12V) 

 Internal Overvoltage 

 Inspect & Adjust (VR2) 

 Power Line Short or Broken 

 Power Line Check 

 Internal Circuit Fault 

 Circuit check or Exchange 

 E - 1 2

 

 Internal Voltage Fault (-12V) 

 Internal Overvoltage 

 Inspect & Adjust (VR3,4) 

 Power Line Short or Broken 

 Power Line Check 

 Internal Circuit Fault 

 Circuit check or Exchange 

 G E n X 

 

 GEN, No.X   (X : 1,2,3) 

 Analog Input Fault   

 Analog Input(AnX) Short or Broken 

 ANx Line Check 

 External Power Detector Fault 

 Power Detector Check 

 Internal Circuit Fault 

 Circuit check or Exchange 

 G E X X

 

 GEN, No.XX   (XX :12,13,23) 

 Analog Input Fault 

 Analog Input(AnXX) Short or Broken 

 ANx,x Line Check   

 External Power Detector Fault 

 Power Detector Check 

 Internal Circuit Fault 

 Circuit check or Exchange 

 G 1 2 3

 

 GEN, NO.1,2,3 

 Analog Input Fault 

 Analog Input(An1,2,3) Short or Broken 

 AN1,2,3 Line Check 

 External Power Detector Fault 

 Power Detector Check 

 Internal Circuit Fault 

 Circuit check or Exchange 

 I n X X

 

 Channel No.XX (1

48) 

 Internal Input Fault 

 Internal Input IC Fault 

 Defective IC Exchange 

 Internal Input Line Short or Broken 

 Board check or Exchange 

 Internal Circuit Fault 

 Circuit check or Exchange 

10 

 o u X X

 

 Channel No.XX (1

40) 

 Internal Output Fault 

 Internal Output IC Fault 

 Defective IC Exchange 

 Internal Output Line Short or Broken 

 Board check or Exchange 

 Internal Circuit Fault 

 Circuit check or Exchange 

 

REMARK : 

NO6, 7, 8 Analog input Fault 

- If the analog input becomes less than 2.4mA, an alarm occurs about 5 seconds later. 

 

Summary of Contents for KT-PPC

Page 1: ...ong J Y Chung V1 2E 2007 08 17 Add REMARK C Y Jeong S W Jeong J Y Chung V1 3E 2008 11 17 Add load balance abnormal function C Y Jeong S W Jeong J Y Chung V1 4E 2009 02 02 Add troubles and correcting m...

Page 2: ...rallel Running by Heavy Load Pref Trip 8 3 2 Auto Parallel Running Cancellation by Light Load 9 3 3 Auto Changeover by BUS No Voltage 10 3 4 Auto Changeover by BUS Abnormal 11 3 5 Auto Parallel Runnin...

Page 3: ...s you find out the cause of the errors in the case of problems so it is easy for you to maintain the power control system You can build electric power control system for various applications by modify...

Page 4: ...0 55 Storing temp 10 70 Weight Approx 5Kg Communication RS 232c serial 1 port CPU Specification Control system Intel 80c196kc 16Bit microcomputer Program system Assemble description system Program me...

Page 5: ...IR9402 30 D01 210 297 mm KTE CO LTD TI 06 R0 2 SYSTEM CONSTRUCTION 2 1 DIAGRAM OF POWER MANAGEMENT CONTROL SYSTEM FOR SHIP REMARK 1 PWC Generator power controller for ship 2 Each PWC is used for contr...

Page 6: ...Controller KT PPC REV 1 6E PAGE 6 OF 25 Doc No TIR9402 30 D01 210 297 mm KTE CO LTD TI 06 R0 2 2 DIAGRAM OF POWER MANAGEMENT CONTROL SYSTEM WITH INCOMING POWER REMARK One unit of PWC used for each ge...

Page 7: ...0 3 SYSTEM FLOW CHARTS 3 1 Auto Parallel Running by Heavy Load Pref Trip Refer to Flowchart 3 2 Auto Parallel Running Cancellation by Light Load Refer to Flowchart 3 3 Auto Changeover by BUS No Voltag...

Page 8: ...Instruction Manual of Programmable Power Controller KT PPC REV 1 6E PAGE 8 OF 25 Doc No TIR9402 30 D01 210 297 mm KTE CO LTD TI 06 R0 3 1 Auto Parallel Running by Heavy Load Pref Trip...

Page 9: ...Instruction Manual of Programmable Power Controller KT PPC REV 1 6E PAGE 9 OF 25 Doc No TIR9402 30 D01 210 297 mm KTE CO LTD TI 06 R0 3 2 Auto Parallel Running Cancellation by Light Load...

Page 10: ...Instruction Manual of Programmable Power Controller KT PPC REV 1 6E PAGE 10 OF 25 Doc No TIR9402 30 D01 210 297 mm KTE CO LTD TI 06 R0 3 3 Auto Changeover by BUS No Voltage...

Page 11: ...Instruction Manual of Programmable Power Controller KT PPC REV 1 6E PAGE 11 OF 25 Doc No TIR9402 30 D01 210 297 mm KTE CO LTD TI 06 R0 3 4 Auto Changeover by BUS Abnormal...

Page 12: ...Instruction Manual of Programmable Power Controller KT PPC REV 1 6E PAGE 12 OF 25 Doc No TIR9402 30 D01 210 297 mm KTE CO LTD TI 06 R0 3 5 Auto Parallel Running by ACB Trip...

Page 13: ...08 09 AN5 No 5 GEN Power 10 11 GND 12 GND 13 F G Frame Ground 14 F G Frame Ground 15 Unused 16 Unused 17 Unused 18 Unused 19 Unused 20 Unused 21 Unused 22 Unused 23 Unused 24 Unused 25 No 1 GEN Auto...

Page 14: ...ady to Start 08 No 1 GEN Run 09 No 2 GEN Run 10 No 3 GEN Run 11 No 1 GEN Stop 12 No 2 GEN Stop 13 No 3 GEN Stop 14 No 1 GEN ACB Close 15 No 2 GEN ACB Close 16 No 3 GEN ACB Close 17 GEN Voltage build u...

Page 15: ...05 GND POWER SUPPLY 06 GND 07 GND 08 GND 09 Unused 10 Unused 11 Unused 12 Unused 13 Unused 14 Unused 15 Unused 16 Unused 17 Unused 18 Unused 19 Unused 20 Unused 21 PPC NORMAL Contact A C 22 23 No 1 A...

Page 16: ...o 1 GEN AUTO LOAD SHIFT 12 No 2 GEN AUTO LOAD SHIFT 13 No 3 GEN AUTO LOAD SHIFT 14 No 1 1st ST BY 15 No 2 1st ST BY 16 No 3 1st ST BY 17 No 1 ENG STOP 18 No 2 ENG STOP 19 No 3 ENG STOP 20 No 1 2nd ST...

Page 17: ...20mA 10 ANALOG INPUT 5 4 20mA 11 GND 12 GND 13 F G Frame Ground 14 F G 15 X 16 X 17 X 18 X 19 X 20 X 21 X 22 X 23 X 24 X 25 No 1 GEN AUTO MODE SELECT INP 01 0 143A AUTO 26 No 2 GEN AUTO MODE SELECT IN...

Page 18: ...P 12 No 2 GEN STOP INP 03 7 205X STOP 13 No 3 GEN STOP INP 04 0 305X STOP 14 No 1 GEN ACB CLOSE INP 04 1 CB1 CLOSE 15 No 2 GEN ACB CLOSE INP 04 2 CB2 CLOSE 16 No 3 GEN ACB CLOSE INP 04 3 CB3 CLOSE 17...

Page 19: ...X 16 X 17 X 18 X 19 X 20 X 21 PPC NORMAL CONTACT A OUT 01 0 22 PPC NORMAL CONTACT C 23 No 1 ACB CLOSE CONTACT A OUT 01 1 24 No 1 ACB CLOSE CONTACT C 25 No 2 ACB CLOSE CONTACT A OUT 01 2 26 No 2 ACB C...

Page 20: ...LOAD SHIFT OUT 03 0 14 No 1 1st ST BY OUT 03 1 15 No 2 1st ST BY OUT 03 2 16 No 3 1st ST BY OUT 03 3 17 No 1 ENG STOP OUT 03 4 18 No 2 ENG STOP OUT 03 5 19 No 3 ENG STOP OUT 03 6 20 No 1 2nd ST BY OU...

Page 21: ...JP4 Communication Method Selection C A JP5 JP6 C B RS 232c Serial Communication JP7 SW8 1 ON OFF 2 ON OFF 3 ON OFF 4 ON OFF 5 ON OFF Remark Default setting value Do not intentional modifying after pu...

Page 22: ...be applied to only KT PPC A type model SW1 SW2 SW3 CONTENT 0 0 0 run Normal operation 1 0 X Unused 1 X No 1 Generator power Kw 2 X No 2 Generator power Kw 3 X No 3 Generator power Kw 4 X Generator to...

Page 23: ...l Overvoltage Inspect Adjust VR2 Power LineShortorBroken Power LineCheck Internal CircuitFault CircuitcheckorExchange 5 E 12 Internal VoltageFault 12V Internal Overvoltage Inspect Adjust VR3 4 Power L...

Page 24: ...Instruction Manual of Programmable Power Controller KT PPC REV 1 6E PAGE 24 OF 25 Doc No TIR9402 30 D01 210 297 mm KTE CO LTD TI 06 R0 8 EXTERNAL FORM...

Page 25: ...heavy dust or metal particles are present in the air store it by using a cover or a package 2 Do not store it in such an area that is subject to corrosive gases 3 Do not sort it in such an area that...

Reviews: