7.0 Select basic program
If necessary, press
Prog
key repeatedly, until the desired basic program
P1 .. P6
is displayed.
Note:
If programs
P1
and
P2
are mixed with programs
P5
and
P6,
time overlapping
can occur.
If the switching times of
P1/P2
and
P5/P6
are not changed, the daily times of
P1/P2
are effective, even on Saturday and Sunday, see table.
Activating program:
Press
SET
key. Display e.g.
P1
is static.
Not activating program:
Press
SET
key. Display e.g.
P1
flashes.
Store by pressing the
Prog
key.
Press
Prog
key until
SET
appears in the clock display.
Now press
SET
key in order to store the program.
8.0 Change basic program
If necessary, press
Prog
key repeatedly, until the desired basic program
P1 .. P6
ist displayed.
Change days:
For the setting period hold the key
d
firmly.
Change the weekdays with the keys
(see table).
Change heating-/set-back time:
For the setting period hold the key
h
or
m
firmly.
Select the desired heating time with the keys
.
Change temperature:
Change the temperature with the keys
.
Store with
Prog
key.
Press
Prog
key until
SET
appears in the clock display.
Now press the
SET
key in order to store the program.
Info:
You can activate a maximum of all
6
basic programms.
9.0
Manual temperature change in automatic operation
Operation:
In automatic mode, an individual temperature change can be set between 5 °C ..
39 °C. This setting is active until the next heating time
P1 .. P6.
After that the
product is controlled according to the time and temperature specification.
Change the temperature setting:
Set the desired temperature with the keys
.
Afterwards release the key.
10.0 ECO program
Operation:
For a period between 1 hour (ECO 1) and 8 hours (ECO 8), a fixed set temperature
of 16° C can be selected. The residual ECO time is displayed. If the ECO program
has expired, the product controls again in accordance with the programmed time
and temperature specification.
Setting in the automatic mode:
Press repeatedly the
ECO
key to set the desired program (ECO 1 ... ECO 8).
E.g. ECO 6
= 6 hours set-back to 16 °C.
Terminate ECO program:
Hold the
ECO
key firmly for approx. 2 secs.
11.0 Program selection switch
Auto =
product controls according to the stored heating program.
Manual temperature change possible
Perm 21 °C =
the product controls permanently at 21 °C.
Manual temperature change is not possible.
Perm Off =
The product is switched off.
Manual temperature change is not possible.
=
Permanent frost prot5 °C.
Manual temperature change is not possible.
12.0 Holiday program
For the duration of a holiday program the clock thermostat controls at a selectable
set-back temperature. Beginning and end of the program is at midnight.
Press the
key briefly.
In how many days is the holiday program to start?
For the setting period hold the key
d
firmly.
Set the period of the holiday program with the keys
.
How long shall the holiday program last?
For the setting period hold the key
d
firmly.
Set the duration of the holiday program with the keys
.
Which temperature is to be controlled during the holiday program?
Set the desired temperature with the keys
.
Store with
SET
key.
Display holiday active: Symbol
appears
In the clock display appears e.g. 00:14, i. e. the duration of the holiday
program is 14 days and ends at midnight.
Cancel holiday program prematurely:
Hold the
key firmly for 2 secs.
13.0 RESET/ total deletion
The changed and stored data revert to the basic setting. Even after a RESET, the
clock thermostat retains the captive basic program. See table: section 6.0.
If no time is set, the product controls at constant 21 °C.
The clock stops and waits for input.
Recommendation: Adjustment with the help of an expert
14.0 Adjustment of the wall alignment
The clock thermostat is adjusted in the factory. If, as a result of its installation
location e. g. cold cement wall, an adjustment is necessary, the temperature
deviation can be corrected.
Correcting temperature deviation:
You can correct the temperature deviation in the range from – 3 °C and +3 °C.
Example:
Temperature difference between measured and controlled
temperature is +2 °C.
Correction:
–2 °C.
Adjustment from automatic mode:
Æ
Hold the
SET
and key firmly for approx. 2 secs.
Æ
For the setting period hold the key
SET
.
Æ
Set the value to be corrected with the keys
.
Æ
Store the changed valve with the
SET
key.
15.0 Setting of the control accuracy
Operation:
The control accuracy can be adjusted to ±0.5 or ±1 K. The basic set-
ting is ±1 K.
Adjustment from the automatic mode:
Æ
Hold the
SET
key and
h
for approx. 2 secs. firmly.
Æ
Release only the key
h
.
Æ
Change the set valve with the key
h
.
Æ
Release the key and store with
SET
key.
16.0 Technical data
Control type
RS Typ 1 in accordance with EN 60730-2-9
Control
hysteresis
Control accuracy
±0.5 K or ±1K
Permitted ambient temperature 0 °C ... + 55 °C
Battery operation
2 x alkaline LR 6
Contact rating
2 (1) A 250 V~ min. 1 mA, 5 V DC
Protection class
II according to EN 60730-1 in flush-fitting
Enclosure type
IP 20 according to EN 60529
Subject to modification