SOL3-1
A)
The collector temperature exceeds the storage temperature by more than the
turn-on threshold (8 K). The collector pump is turned on.
B)
The collector temperature dropped below the turn-off threshold (SF + 4 K). The
collector pump is turned off.
C)
The collector temperature exceeds the turn-on threshold again. The pump is
turned on as soon as the minimum idle time elapses.
D)
The collector temperature dropped and falls below the turn-off threshold again
(SF + 4 K). The collector pump is turned off.
E)
The collector temperature exceeds the storage temperature by more than the
turn-on gap (8 K). The collector pump is turned on.
F)
The collector temperature quickly dropped below the turn-off threshold again.
The pump remains running as long as the minimum running time has not
elapsed.
EB_37381_SOL3-1_EN002
19
Figure 3: temperature chart