5 Installation at Site
5.1 Safety regulations
DANGER
Improper installation in potentially explosive atmospheres
Explosion hazard!
Damage to the pump set!
▷
Comply with the applicable local explosion protection regulations.
▷
Observe the information in the data sheet and on the name plates of pump and
motor.
5.2 Installation
Install pressure booster systems either in the technical equipment room or in a well-
ventilated, frost-free, lockable room used for no other purpose. No harmful gases are
allowed to enter the place of installation. An adequately sized drain (leading to a
sewer or equivalent) must be provided.
The system is designed for a maximum ambient temperature of 0 °C to +40 °C at a
relative humidity of 50 %.
NOTE
Do not install pressure booster systems next to sleeping or living quarters.
The anti-vibration mounting of the pressure booster system provides adequate
insulation against solid-borne noise. If expansion joints (see accessories) are used for
damping vibrations, their fatigue strength (endurance limit) must be given due
consideration. Expansion joints must be installed to allow quick and easy
replacement.
5.3 Checks to be carried out prior to installation
Place of installation
WARNING
Installation on mounting surface which is unsecured and cannot support the load
Personal injury and damage to property!
▷
Use a concrete of compressive strength class C12/15 which meets the
requirements of exposure class XC1 to EN 206-1.
▷
The mounting surface must have set and must be completely horizontal and
even.
▷
Observe the weights indicated.
NOTE
The anti-vibration mounts of the pressure booster system provide adequate
insulation against solid-borne noise.
Thanks to level-adjustable feet (KSB accessory) the pressure booster system can also
be installed in horizontal position on uneven floors.
1.
Check the structural requirements.
All structural work required must have been prepared in accordance with the
dimensions stated in the outline drawing.
5 Installation at Site
16 of 40
Surpress Feu SFE.3