Pump Switchgear / Control Systems
LevelControl Control Units
4
LevelControl Basic 2
4041.5/12-EN
Pump Switchgear / Control Systems
LevelControl Control Units
LevelControl Basic 2
General description
Level-dependent pump control and monitoring unit with
display for either 1 or 2 pumps.
LevelControl Basic 2 can be used for tank drainage and tank
filling.
1)
.
The ATEX-compliant version of the control unit can be used for
pumps in potentially explosive atmospheres. The control unit is
installed outside the potentially explosive atmosphere.
Main applications
Fields of applications:
▪
Grey water
▪
Waste water
▪
Service water supply
▪
Waste water lifting units / pump stations
Applications:
▪
Draining of pits, shafts, etc.
▪
Dewatering
▪
Drainage
▪
Water extraction
▪
Fluid transport
▪
Disposal
Compatible pumps:
▪
Ama-Drainer
▪
Ama-Drainer-Box (LevelControl Basic 2 included in the
scope of supply)
▪
MK
▪
Ama-Porter
▪
Amarex
▪
Amarex N
▪
Amarex KRT
▪
CK pump stations (LevelControl Basic 2 included in the
scope of supply in some cases)
▪
mini-Compacta / Compacta (LevelControl Basic 2 included
in the scope of supply)
▪
Sewatec / Sewabloc
▪
Etaline
▪
Etanorm / Etabloc
▪
Other pumps on request
Variants
LevelControl Basic 2 is available in 2 variants:
▪
Type Basic Compact (plastic housing)
▪
Type Basic Control Cabinet (sheet steel housing)
Type Basic Compact (BC)
Pump control and monitoring unit with
display in compact housing for 1 or 2
pumps with power ratings of up to 4 kW
each. Level detection performed using at
least one float switch, an analog sensor
4-20 mA or an integrated pressure sensor
(pneumatic or bubbler control up to
2 mwc
2)
), for motors with DOL starting.
Type Basic Control Cabinet (BS)
Pump control and monitoring unit with
display in steel housing for 1 or 2 pumps.
Level detection performed using at least
one float switch, an analog sensor 4-20 mA
or an integrated pressure sensor
(pneumatic or bubbler control) for motors
with DOL starting or star-delta starting.
1
Using float switches, digital level switches or 4-20 mA analog sensors
2
For bubbler control in BC housing, option O1 (master switch in BC housing) cannot be used.
Summary of Contents for LevelControl Basic 2
Page 1: ...Level Control Unit LevelControl Basic 2 Type Series Booklet...
Page 36: ......