![KSB Calio-Therm NC Installation & Operating Manual Download Page 25](http://html1.mh-extra.com/html/ksb/calio-therm-nc/calio-therm-nc_installation-and-operating-manual_2006581025.webp)
WARNING
Hot surface
Risk of injury!
▷
Allow the pump set to cool down to ambient temperature.
WARNING
Risk of hot fluid escaping as a result of incorrect assembly/ dismantling
Risk of burns!
▷
Do not damage the seal elements and sealing surfaces.
7.3.2
Removing the complete pump set from the piping
DANGER
Work performed on an energised terminal box
Danger of death from electric shock!
▷
Switch off the power supply at least 5 minutes prior to commencing work and
ensure that it cannot be switched on again unintentionally.
DANGER
Pump acting as a generator when running in reverse
Danger to life from hazardous induction voltage at the motor terminals!
▷
Prevent the fluid from flowing back by closing the shut-off elements.
✓
The relevant notes and steps have been observed/carried out.
✓
The pump has cooled down to ambient temperature.
✓
A container for collecting the fluid has been positioned underneath the pump
set.
1.
De-energise the pump set (disconnect the motor) and ensure that it cannot be
re-energised unintentionally.
2.
Close the shut-off elements.
3.
Disconnect the discharge and suction nozzles from the piping.
4.
Depending on the pump/motor size, remove the supports from the pump set.
5.
Remove the complete pump set from the piping.
7 Servicing/Maintenance
Calio-Therm NC
25 of 30