3 Description
10 of 16
BACnet MS/TP Gateway
Type-Instance
Object name
Value
Read/Write
Description
-
R
KSB Calio BACnet
-
R/W
CSV Config File ASCII plain text
-
R
BINARY DATA file compressed
-
R
SRAM DATA buffer
-
R
Pico BAS program file
compressed
-
R/W
Pico program file
Online / Error
R
FP:19200,'E',8,1,'B',1000,1000
Running / Halted
R/W
KSB Calio adaption (c)
V20150805 HHO-uha
Eco-Mode
Const-Pr
Propor-Pr Boost
R/W
Selecting the operating mode
All describable properties (see PICs) with the exception of PresentValue are
permanently saved in the gateway’s flash memory.
To ensure that values are written to the pump as required, PRG-1 P-Basic Program
must display the value “Running”.
AV-1 Calio_Setpoint, BV-1 Calio_Start/Stop and MV-1 Calio_OpMode can only write
values to the pump if Modbus is activated at the pump.
The gateway checks this periodically every 3 minutes.