Installation, Operation, & Maintenance for FC Horizontal Basic

Page: 3 of 3

Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | [email protected] | www.krueger-hvac.com

Operation and Control 

The unit is normally wired to operate with a four-position 

fan selector switch: 

- OFF 

- HI High Fan Speed 

- MED Medium Fan Speed 

- LO Low Fan Speed 

An external thermostat (normally wall mounted) is used to 

select the desired room temperature.

Where the unit is provided with electric heating (optional), 

the external heat/cool changeover switch has to be set in 

the  heat  position  to  enable  the  thermostat  to  switch  the 

heater on when the room temperature drops below the set 

point.

Maintenance

 

CAUTION:  All  maintenance  must  be 

performed  by  a  trained,  experienced 

service technician. 

To  prevent  electrical  shock,  disconnect  electric 

power to system at main fuse or circuit breaker 

box until maintenance is complete. 

While  the  HFH  model  is  fully  accessible,  maintenance 

on  the  HFEC,  HFHP,  and  HFI  models  is  performed  by 

removing the access panel. 

The unit must be isolated 

from the power supply. 

Filter ( HFHP, HFEC, & HFI )

 

The  useful  life  of  the  throw-away  filter  depends  on  the 

environment  in  which  the  unit  is  operating.  However,  it 

is recommended to change the filter at least every three 

months. 

To replace the filter (HFEC & HFI) , remove the access 

panel, unfasten the velcro-backed filter-retaining channels, 

remove  channel  to  replace  the  filter.  For  the  HFHP, 

unfasten the filter retains and remove the filter.

Drain Pan

 

Periodic cleaning of the drain pan is essential, especially 

in  high  humidity  areas.  Remove  all  foreign  material  to 

ensure the free flow of condensation.

Coils

 

Clogged coils are a major cause of unit failure. Periodic 

inspection should take place at least once a year.

1. 

Dirty  coils  should  be  cleaned  with  the  appropriate 

brush and vacuum cleaner or compressed air.

Electric Motor(s)

 

A  yearly  motor  inspection  should  take  place  and  the 

following is recommended: 

1. 

Clean  all  dirt  and  lint  with  a  brush  and/or  vacuum 

cleaner. 

Strainer (Optional) 

The frequency that the strainer has to be cleaned depends 

on the overall conditions of the distribution piping system. 

However,  frequent  cleaning  is  recommended  during  the 

installation  and  start-up  stages  and  thereafter  at  every 

summer/winter season change.

1. 

Open the clean-out cap on the strainer to release the 

dirt. Close it once clear liquid is observed.

Pete’s Plug (Optional) 

The plug is installed as an aid in measuring pressure and 

temperature. See complete explanation page for details. 

Electric Heater(s) (Optional)

 

The heater is fastened to the fan deck at the blower outlet 

with sheet metal screws. In case of heater failure, follow 

the procedure described below:

1. 

Disconnect  all  power  sources  before  attempting  to 

open  the  unit.  Check  all  electrical  connections  to 

ensure the unit is fully isolated.

2. 

Unscrew the fan deck and expose the heater(s). 

3. 

If the thermal cut-out switch is defective, disconnect 

the  electrical  wires  and  unscrew  it  from  the  heater 

assembly.  Obtain  a  replacement  from  Krueger  and 

reinstall.

4. 

If  the  heating  element  (the  spiral  resistance  wire)  is 

burned out, unscrew the heater assembly from the fan 

deck, disconnect the terminals and replace with a new 

heater obtained from Krueger.

When contacting Krueger for replacement parts, 

always  refer  to  the  complete  Model  and  Serial 

numbers on the Serial Plate.

!