Indicates ” Alarm setting mode”
To set alarm point for Hi
1_Hindicates Hi setting,1_Lindicates Low setting.
Alarm condition of 1_Hor1_Lis to be selected in the Condition setting mode.
Figure shifted by and set by key.
Value can be set within range of −9999〜+9999digits.
During setting operation, Hi LCD display lighting.
To set alarm point for Lo
2_Hindicates Hi setting,2_Lindicates Low setting.
Alarm condition of 2_Hor2_Lis to be selected in the Condition setting mode.
Figure shifted by and set by key.
Value can be set within range of −9999〜+9999digits.
During setting operation, Lo LCD display lighting.
Indicates ” Alarm condition setting mode”
To set alarm condition for Hi.
Set by key.
1_H:to set Hi alarm point.
1_L:to set Low alarm point.
During setting operation, Hi LCD display lighting.
To set hysteresis for Hi output to return from On to Off.
Figure shifted by key and set by key.
During setting operation Hi LCD display lighting.
Mode change for Positive Logic or Negative Logic
To set alarm condition for Lo.
Set by key.
2_H:to set Hi alarm point.
2_L:to set Low alarm point.
To set hysteresis for Lo output to return from On to Off.
Figure shifted by key and set by key.
During setting operation Lo LCD display lighting.
Mode change for Positive Logic or Negative Logic
To set delay time for Hi and Lo output to move from Off to On or On to Off.
on.d :To set delay time to move from Off to On.
oFF.d:To set delay time to move from On to Off.
Set by key.
Delay time can be set within range of 0〜9999 sec.
Figure shifted by key and set by key.
Alarm active or non active mode
Backlight blink or not when alarm value on the display
8. Setting menu
- 7 -