The solenoid valve does not close securely,
the flow downstream of the solenoid valve
does not stop.
!
Valve seat is dirty.
•
Clean the valve seat, see page 6 (Mainte-
•
Install a filter upstream of the solenoid valve.
!
Valve seat is damaged.
•
Remove the unit and return it to the manufacturer.
!
Valve seal is damaged or hardened.
•
Remove the unit and return it to the manufacturer.
!
Guiding elements bent. Incorrect handling when
installing the unit.
1
2
•
Remove the unit and return it to the manufacturer.
Technical data
Gas types: natural gas, town gas, LPG (gaseous),
biologically produced methane (max. 0.1 %-by-
vol. H
2
S, VG..M only) or clean air; other gases on
request. The gas must be dry in all temperature
conditions and must not contain condensate.
Max. inlet pressure p
u
: see type label.
Opening time:
VG..N: quick opening, ≤ 1 s.
VG..L: slow opening, 10 s.
Closing time:
VG..N, VG..L: ≤ 1 s.
Ambient temperature: -20 to +60°C (5 to 140°F).
No condensation permitted.
Long-term use in the upper ambient temperature
range accelerates the ageing of the elastomer ma-
terials and reduces the service life (please contact
manufacturer).
Storage temperature: -20 to +40°C (68 to 104°F).
Safety valve:
Class A, Group 2 pursuant to EN 161.
Mains voltage:
220/240 V AC, +10/-15%, 50/60 Hz,
120 V AC, +10/-15%, 50/60 Hz,
24 V DC, +10/-15%.
Electrical connection of VG 10/15
–
40/32:
plug with socket to EN 175301-803,
cable gland: PG 11,
connection terminal: 2.5 mm
2
.
Electrical connection of VG 40
–
65:
plug with socket to EN 175301-803,
cable gland: PG 13.5,
connection terminal: 2.5 mm
2
.
Enclosure: IP 54.
Duty cycle: 100%.
Power factor of the solenoid coil: cos φ = 1.
Power consumption:
Voltage
Type
24 V DC
120 V AC
220 V AC
240 V AC
VG 15
32 VA / W 38 VA / W
VG 15/12R18
31 VA / W 37 VA / W
VG 20, VG 25, VG 40/32 36 VA / W 42 VA / W
VG 40
73 VA / W 86 VA / W
VG 50, VG 65
85 VA / W 99 VA / W
Switching frequency: max. 30/min.
Valve housing: aluminium.
Valve disc: NBR.
Internal thread: Rp to ISO 7-1.
Flange: ISO 7005 (DN 65 to DIN 2501), PN 16.
Air flow rate V
.
(Q) for pressure loss Δp = 1 mbar.
VG 40
24.0
VG 40/33
13.5
VG 50
37.0
VG 50/39
23.0
VG 50/65
48.0
VG 65
57.0
VG 65/49
35.0
VG 80
85.0
VG 100
130.0
VG 10/15
3.0
VG 15
3.8
VG 15/12
2.3
VG 20
8.0
VG 25
10.0
VG 25/15
3.8
VG 40/32
18.0
V
.
(Q) [m
3
/h]
V
.
(Q) [m
3
/h]
∆
p = 1 mbar
Designed lifetime
This information on the designed lifetime is based on
using the product in accordance with these operating
instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture) in
accordance with EN 13611, EN 161 for VG:
Type
Designed lifetime
Switching
cycles
Time
[years]
VG 10/15 – 25
200,000
10
VG 40/32
100,000
10
VG 40 – 80
100,000
10
VG 100
50,000
10